Plan Review Notes
Plan Review Notes For Permit 06060432
Permit Number 06060432
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-23 00:00:00********** PROVISO ***********
  
 ** THE FOLLOWING SHALL BE REVISED BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
  
 1) PLEASE PROVIDE A REVISED PANEL
 SCHEDULE LISITNG ALL THE MIN REQUIRED
 DEDICATED CIRCUITS AS SHOWN ON PLANS.
 FRIG, MICRO, SMALL APPL, BATH,ETC
 210.52B1,210.11C1,210.11C3,220.16,408.4
 ETC.
  
 2) PLEASE SEE THAT ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/ GFI
 PROTECTED.
 2108A6
  
 3) PLEASE SEE SPACING SHALL MEET
 210.52C1-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  