Plan Review Notes
Plan Review Notes For Permit 06060425
Permit Number 06060425
Review Stop B
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00 
  
  
 DENIED
  
 1) SHUTTER #4 IS IN THE END ZONE(5) AND
 HAS A PRESSURE OF -72.16 AND 1 SPAN OF
 7'-7" THIS DOES NOT MEET THE MAX SLAT
 SPAN AS REQUIRED ON TABLE 1 PAGE 4
  
 2) THERE IS CONFUSION BETWEEN ENGINEERED
 DRAWING AND SKETCH WITH THE SIZE OF
 OPENING FOR #5. SKETCH AND SCHEDULE
 HAS 1 OPENING, ENGINEERING HAS 2. IF WE
 FOLLOW THE ENGINEERED SHEET THE SLAT
 SPAN EXCEEDS THE MAX FOR STATED PRESSURE
 ON OPENING #4, IF IT IS 1 OPENING IT
 WOULD THEN BE IN ZONE 5 BUT WILL HAVE A
 LARGER AREAAND A NEW PRESSURE SHOULD
 BE ASSIGNED. WITH 2 SPANS IT STILL MAY
 NOT MEET THE MAX ALLOWABLE SPAN ON PG. 4
  
 3) STORM BAR SIZE SCHEDULE ON PAGE 7 ARE
 NOT SHOWN FOR WORST CASE PRESSURES AND
 CORRECT LENGTHS. ARE THEIR HEADERS OR
 ARE THEY COMPLETE HEIGHT TO UNDER SIDE
 OF DECK ABOVE OR BOTH? PLEASE SHOW ON
 PAGE 3
  
 4) MULLION AND HEADER SIZES AND SPANS
 WILL DEPEND ON THE ANSWERS TO NOTES 1&2,
 PLEASE FILLOUT AS REQUIRED BY
 ENGINEERING
  
  
 BLDG PLAN REVIEW