Plan Review Notes For Permit 06060425 |
Permit Number |
06060425 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-22 00:00:00 | | | | | | | DENIED | | | | 1) SHUTTER #4 IS IN THE END ZONE(5) AND | | HAS A PRESSURE OF -72.16 AND 1 SPAN OF | | 7'-7" THIS DOES NOT MEET THE MAX SLAT | | SPAN AS REQUIRED ON TABLE 1 PAGE 4 | | | | 2) THERE IS CONFUSION BETWEEN ENGINEERED | | DRAWING AND SKETCH WITH THE SIZE OF | | OPENING FOR #5. SKETCH AND SCHEDULE | | HAS 1 OPENING, ENGINEERING HAS 2. IF WE | | FOLLOW THE ENGINEERED SHEET THE SLAT | | SPAN EXCEEDS THE MAX FOR STATED PRESSURE | | ON OPENING #4, IF IT IS 1 OPENING IT | | WOULD THEN BE IN ZONE 5 BUT WILL HAVE A | | LARGER AREAAND A NEW PRESSURE SHOULD | | BE ASSIGNED. WITH 2 SPANS IT STILL MAY | | NOT MEET THE MAX ALLOWABLE SPAN ON PG. 4 | | | | 3) STORM BAR SIZE SCHEDULE ON PAGE 7 ARE | | NOT SHOWN FOR WORST CASE PRESSURES AND | | CORRECT LENGTHS. ARE THEIR HEADERS OR | | ARE THEY COMPLETE HEIGHT TO UNDER SIDE | | OF DECK ABOVE OR BOTH? PLEASE SHOW ON | | PAGE 3 | | | | 4) MULLION AND HEADER SIZES AND SPANS | | WILL DEPEND ON THE ANSWERS TO NOTES 1&2, | | PLEASE FILLOUT AS REQUIRED BY | | ENGINEERING | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|