Plan Review Notes
Plan Review Notes For Permit 06060363
Permit Number 06060363
Review Stop P
Sequence Number 1
Notes
Date Text
2006-07-22 00:00:00NOT ENOUGH INFORMATION ON PLANS TO DO A
 PLUMBING PLAN REVIEW.
 1.PLEASE PROVIDE ON PLANS THE SCOPE OF
 PLUMBING WORK TO BE DONE
 2.PERMIT APPLICATION, DESCRIBSION OF
 WORK; WHAT CONNECTIONS OUTSIDE THE UNIT
 WALLS WILL BE ALTERERD, PLEASE SHOW ON
 PLANS.
 3.PLEASE SHOW DETAIL OF AUTOMATIC
 CLOTHES WASHER PLUMBING. CLOTHES WASHER
 HOOK UP SHALL MEET THE REQUIREMENTS OF
 THE FBC-2004 PLUMBING CODE SECTION
 406.3.
 4.WHERE IS SOURCE OF HOT WATER REQUIRED
 BY CODE. NOT SHOWN ON PLAN.
 THIS REVIEW INCLUDES ALL PERMIT
 APPLICATIONS SUBMITED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695