2007-05-14 09:20:02 | ** UNSAT ** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE SEE 210.4 AS THE DISHWASHER AND |
| DISPOSAL SEEM TO BE FEEDING THE SAME YOKE WHICH WOULD |
| REQUIRE 2-POLE BREAKER.THE BOTH ARE CURRENTLY BEING |
| SHOWN AS SINGLE POLE BREAKERS> |
| PLEASE ADJUST BREAKER(S) OR PLANS FOR THE DEVICES. |
| |
| 2) NOTE: PLEASE SEE MISSING GFI RECEPTACLES DEVICES FOR |
| NEW COUNTER SPACE AREAS PER 210.52C1. |
| |
| 3) NOTE: PLEASE SEE BATH CIRCUIT IS BEING SHOWN WITH |
| THE CORRECT CONDUCTOR SIZE OF #12, HOWEVER THE BREAKER |
| SIZE IS SHOWN AS 15AMP? |
| PLEASE SEE 210.11C3, 210.52D |
| |
| 4) NOTE: PLEASE SEE THE PLANS ARE MISSING THE OUTLET |
| FOR RANGE/OVEN. |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE CORRELATE THE LOAD CALCULATIONS WITH |
| THE ITEMS ON THE PANEL SCHEDULES. PLEASE SEE THERE ARE |
| MANY ITEMS ON CALCS WHICH ARE NOT ON PANEL SCHEDULE? |
| NEC 220, 408.4, 310.16, 240.4. |
| FBC 106.3.5.4 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |