2007-07-16 10:53:37REV FOR FINAL.
 CHANGED THE ELECTRICAL ENGINEER OF RECORD. LTR FOR
 CHANGE SUBMITTED.
  
 REDLINED LOAD FOR SMALL APPL ON PANEL SCHEDULE. SHOWS
 450VA WHEN THIS SHOULD BE 1500VA AS STATED ON LOAD
 CALCULATIONS.
  
 REDLINED BATH RECEPT, VIF 210.52D. RECEPTACLE IS SHOWN
 AS EXISTING, HOWEVER IF VANITY IS NEWLY LOCATED, GFI IS
 TO BE WITHIN 3FT OF LAV.