Plan Review Notes
Plan Review Notes For Permit 06060332
Permit Number 06060332
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-06 00:00:00** REDLINED PLANS, AS RISER SHOWS 125A
 PANEL AND PANEL SCHEDULE IS SHOWN AS
 200A?
 MAIN BUILDING PLANS, INDICATE THESE WILL
 BE CHNAGED FROM THE EXISTING 100A'S TO
 125A PANELS ON THE MAIN BUILDING PERMIT
 APPLICATION TO UPGRADE SERVICE(S).
  
 ** THIS IS TO BE REVISED BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]