Notes |
Date |
Text |
2007-08-01 19:59:54 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE PLANS ONLY INDICATE ONE SMALL | | APPLIANCE CIRCUIT WHEN LOAD CALCULATIONS INDICATE TWO. | | PLEASE ALSO SEE PANEL SCHEDULE INDICATE A DINING ROOM | | RECEPTACLE CIRCUIT WHICH IS REQUIRED TO BE FIGURED AS | | ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS. PLEASE | | KNOW AS THIS APPEARS TO BE A THIRD SMALL APPLIANCE | | CIRCUITS, PLEASE ADJUST LOAD CALCULATIONS. 210.52B1, | | 210.11C1, 220.16 | | | | ** PLEASE BE SURE TO SUBMIT LETTERS BACK WITH REVISED | | PLANS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|