Plan Review Notes
Plan Review Notes For Permit 06060323
Permit Number 06060323
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-23 10:27:08*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE LOADS AND CIRCUITS FOR ONE OR
 MORE OF THE SMALL APPLIANCE CIRCUITS INCLUDING DINING
 ROOM ARE TO BE SHOWN AND FIGURED AT 1500VA PER
 210.52B1, 210.11C1, 220.16
 PLEASE BE SURE TO ADJUST BOTH THE PANEL SCHEDULE AND
 LOAD CALCULATIONS.
 PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE A 15AMP
 DINING ROOM CIRCUIT. (ALREADY CONTAINS #12 AND NEEDS
 THE ADJUSTMENT OF THE LOADS AND OCP.
  
 2) NOTE: PLEASE SEE NFPA-72, THE SMOKE DEVICES ARE
 SHOWN AS SMOKE DETECTORS, YET THESE SEEM TO BE SMOKE
 ALARMS. PLEASE SEE DEFINITIONS FOR THESE DEVICES UNDER
 NFPA-72.
 PLEASE ADJUST AS PLANS ARE COMING BACK FOR OTHER
 COMMENTS.
  
 3) NOTE: PLEASE BE SURE TO SUBMIT LETTERS WHICH ARE
 ATTACHED TO PLANS WHEN RESUBMITTING.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  