Date |
Text |
2006-07-15 00:00:00 | ******* UNSAT ******* |
| |
| 1) NOTE: PLEASE SEE RISER IS NOW BEING |
| SHOWN COMPLETELY REVISED FROM PREVIOUS |
| RISERAND IS NOW SHOWING "TWO' ATS'S?? |
| PLEASE SEE RISER SHOWS A NOTE WHICH |
| MENTIONS TWO EXSITING PANELS, YET, RISER |
| SHOWS ONE AS A MAIN DISCONNECT? |
| PLEASE SEE NEW MAIN SHOWS CONNECTIONS TO |
| BOTH ATS UNITS. ONE SE RATED AND THE |
| OTHER NOT SE RATED?? |
| |
| PLEASE SEE THE SE RATED ATS AS ONLY |
| DISCONNECTS THE POWER ON THE FPL/LINE |
| SIDE AND DOES NOT DISCONNECT POWER ON |
| THE GEN/FEEDER SIDE AS REQUIRED BY |
| 225.31-225.39 |
| PLEASE KNOW, PLANS DO NOT INDICATE IF |
| THE EXISTING 200A PANEL IS MLO OR MCB |
| AND IF THIS PANEL IS GROUPED WITH THE |
| OTHER MAINS. |
| 230.72,225.34 |
| PLEASE KNOW, IF A MAIN DISCONNECT IS |
| LOCATED AHEAD OF THE ATS, THEN THE ATS |
| DOES NOT NEED TO BE SE RATED AND ONLY |
| RATED AS "SERVICE EQUIPMENT". |
| PLEASE EXPLAIN RATIONAL OF THE 2ND NON |
| SE RATED ATS? WHY IS THIS BEING USED AS |
| THIS IS SHOWN FEEDING THE SAME SE RATED |
| ATS. |
| PLEASE ALSO SEE THE NEW MAIN DISCONNECT |
| IS BEING SHOWN FEEDING THE NEW SE RATED |
| ATS AND THE NON SE RATED ATS? |
| SPECS SHOULD REFLECT THE ATS BEING |
| INSTALLED. |
| |
| ** PLEASE KNOW, RISER NOW ALSO MENTIONS |
| TO ISOLATE NEUTRALS IN PANEL "IF |
| NECESSARY". PLEASE KNOW, ALL NEUTRALS |
| AND EQUIPMENT GROUNDING CONDUCTORS SHALL |
| BE SEPARATED AFTER THE FIRST MEANS OF |
| DISONNECT AS NOT TO PARALLEL THE |
| NEUTRAL. |
| 250.6,250.24B |
| |
| 2) NOTE: PLEASE KNOW, THE LATEST LTR |
| FROM GENERAC FOR MIN CLEARENCES LEAVES |
| THE REQUIRED MIN CLEARNECES TO THE AHJ, |
| AND AS STATED AND RECOMMENDED ON A LTR |
| OBTAIN FROM GENERAC, THE MIN CLEARNECES |
| FOR AIR COOLED UNITS, SHALL BE 3' AND |
| LIQUID COLLED UNITS SHALL BE 5' FROM ANY |
| SURROUNDING WALLS , ETC. |
| THIS IS A NOTE FOR ANY INSTALLATIONS. |
| |
| 3) NOTE: PLEASE SPECIFY THE ELEVATION OF |
| THE SLAB FOR THE NEW GEN. THE LTR WHICH |
| MENTIONS THE FLOOD ZONEIS OK, HOWEVER |
| SLAB ELEVATIONS SHOULD BE NOTED OR |
| SHOWN. PLEASE SEE AN ELEV OF 12 IS SHOWN |
| IN LTR, BUT UNCLEAR IF THIS IS 12' |
| (FEET). IF SO, ELEV SHOULD BE NOTED ON |
| SLAB DETAIL TO BE 12'6" MIN. PLEASE |
| KNOW, AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED BEFORE FINAL. |
| |
| |
| 4) NOTE: PLEASE MAKE PLANS INTO TWO SETS |
| AND REMOVE ANY OLD/VOIDED SHEETS FROM |
| SETS AND LEAVE ANY PREVIOUSLY STAMPED |
| SHEETS BE OTHER REVIEWER(S) IN SETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |