Plan Review Notes
Plan Review Notes For Permit 06060302
Permit Number 06060302
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-15 00:00:00******* UNSAT *******
  
 1) NOTE: PLEASE SEE RISER IS NOW BEING
 SHOWN COMPLETELY REVISED FROM PREVIOUS
 RISERAND IS NOW SHOWING "TWO' ATS'S??
 PLEASE SEE RISER SHOWS A NOTE WHICH
 MENTIONS TWO EXSITING PANELS, YET, RISER
 SHOWS ONE AS A MAIN DISCONNECT?
 PLEASE SEE NEW MAIN SHOWS CONNECTIONS TO
 BOTH ATS UNITS. ONE SE RATED AND THE
 OTHER NOT SE RATED??
  
 PLEASE SEE THE SE RATED ATS AS ONLY
 DISCONNECTS THE POWER ON THE FPL/LINE
 SIDE AND DOES NOT DISCONNECT POWER ON
 THE GEN/FEEDER SIDE AS REQUIRED BY
 225.31-225.39
 PLEASE KNOW, PLANS DO NOT INDICATE IF
 THE EXISTING 200A PANEL IS MLO OR MCB
 AND IF THIS PANEL IS GROUPED WITH THE
 OTHER MAINS.
 230.72,225.34
 PLEASE KNOW, IF A MAIN DISCONNECT IS
 LOCATED AHEAD OF THE ATS, THEN THE ATS
 DOES NOT NEED TO BE SE RATED AND ONLY
 RATED AS "SERVICE EQUIPMENT".
 PLEASE EXPLAIN RATIONAL OF THE 2ND NON
 SE RATED ATS? WHY IS THIS BEING USED AS
 THIS IS SHOWN FEEDING THE SAME SE RATED
 ATS.
 PLEASE ALSO SEE THE NEW MAIN DISCONNECT
 IS BEING SHOWN FEEDING THE NEW SE RATED
 ATS AND THE NON SE RATED ATS?
 SPECS SHOULD REFLECT THE ATS BEING
 INSTALLED.
  
 ** PLEASE KNOW, RISER NOW ALSO MENTIONS
 TO ISOLATE NEUTRALS IN PANEL "IF
 NECESSARY". PLEASE KNOW, ALL NEUTRALS
 AND EQUIPMENT GROUNDING CONDUCTORS SHALL
 BE SEPARATED AFTER THE FIRST MEANS OF
 DISONNECT AS NOT TO PARALLEL THE
 NEUTRAL.
 250.6,250.24B
  
 2) NOTE: PLEASE KNOW, THE LATEST LTR
 FROM GENERAC FOR MIN CLEARENCES LEAVES
 THE REQUIRED MIN CLEARNECES TO THE AHJ,
 AND AS STATED AND RECOMMENDED ON A LTR
 OBTAIN FROM GENERAC, THE MIN CLEARNECES
 FOR AIR COOLED UNITS, SHALL BE 3' AND
 LIQUID COLLED UNITS SHALL BE 5' FROM ANY
 SURROUNDING WALLS , ETC.
 THIS IS A NOTE FOR ANY INSTALLATIONS.
  
 3) NOTE: PLEASE SPECIFY THE ELEVATION OF
 THE SLAB FOR THE NEW GEN. THE LTR WHICH
 MENTIONS THE FLOOD ZONEIS OK, HOWEVER
 SLAB ELEVATIONS SHOULD BE NOTED OR
 SHOWN. PLEASE SEE AN ELEV OF 12 IS SHOWN
 IN LTR, BUT UNCLEAR IF THIS IS 12'
 (FEET). IF SO, ELEV SHOULD BE NOTED ON
 SLAB DETAIL TO BE 12'6" MIN. PLEASE
 KNOW, AN ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL.
  
  
 4) NOTE: PLEASE MAKE PLANS INTO TWO SETS
 AND REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND LEAVE ANY PREVIOUSLY STAMPED
 SHEETS BE OTHER REVIEWER(S) IN SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  