2006-06-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SEE SITE SURVEY WHICH
 WILL REQUIRE ALL SETBACKS AND DIMENSIONS
 FROM DWELLING AND PROPERTY LINES. PLEASE
 SEE THAT THE CLEARENCS OF THE GEN CAN
 NOT BE VERIFIED AT THIS TIME.
 215.5
  
 2) NOTE: PLEASE PROVIDE A SERVICE
 ENTRANCE RATED ATS WHICH DISCONNECTS
 POWER FROM FPL. SPECS SEEM TO INDICATE
 THIS, BU NOT CLEAR.
 CAN NOT VEIRFY THE MEANS OF DISCONNECT
 FROM THE FEEDERS FROM THE GEN. PLEASE
 SEE 230.76,230.79, 230.70
 PLEASE SEE 225.31-225.39 WHICH REQUIRES
 A DISC. PLEASE VERIFY IF THE EXSITING
 PANEL AS SHOWN IS LOCATED AT ATS
 LOCATION AND CONTAINS A MCB?
  
 3) NOTE: PLEASE INDICATE LOCATION OF ALL
 EQUIPMENT ON A LAYOUT FOR HOUSE.
 215..
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE ALSO INDICATE THE RATING FOR ATS.
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SHOW HEAT LOADS AT 100% OR
 PROVIDE LOAD SHEDDING. ** AS SHOWN EVEN
 AT 100%, THERE IS NOT A LOAD ISSUE FOR
 GEN.
 702.5,220, ETC.
 215.5
  
 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE
 LICENSE CONTRACTOR SHALL PRINT NAME AND
 SIGN PLANS.
 FBC 106.2.1, 106.3.2.1 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
  
 7) NOTE: PLEASE BE SURE THE MANUFACTURES
 SPECS / CUT SHEETS SHALL INDICATE THE
 MIN CLEARENCES SET BY THE MANUFACTURE.
 215.5
  
 8) NOTE: PLEASE SUBMIT THE ELEVATION OF
 GENERATOR.FYI, IF IN A FLOOD ZONE, MUST
 BE 6" ABOVE BFE.
  
  