2006-08-17 00:00:00 | *** DENIED *** | | 1) AS REQUESTED IN LAST REVIEW 6-19-06 | | NOTE #2, PLEASE PROVIDE FRESH AIR | | CALCULATIONS, SEE 2004 FBC/M 403.3. | | 20 CFM PER OCCUPANT IS NOT A | | CALCULATION. PLEASE ALSO SHOW HOW MANY | | CFM'S. ARE TO GO TO EACH AHU SO AIR | | BALANCING MAY BE DONE PROPERLY. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|