Plan Review Notes
Plan Review Notes For Permit 06060297
Permit Number 06060297
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-14 00:00:00DENIED;
 1.ADD NOTE TO PAGE A-2; "IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM DEAD
 ENDS ARE NOT PERMITED. DEMO PLUMBING
 INSPECTION REQUIRED".
 2.SANITARY AND WATER RISERS DIAGRAMS
 REQUIRED ON DRAWING PER FBC-2004 CHAPTER
 1 SEC. 106.3.5.1.3. PLEASE SIZE ALL
 PIPES.
 3.MINIMUM PLUMBING FIXTURES; SHOW
 COMPIANCE ON PLANS TO MINIMUM PLUMBING
 FIXTURES REQUIRED PER. TABLE 403.1. LIST
 ON PLANS.
 4.AUTOMATIC CLOTHES WASHER DRAIN
 REQUIRED TO BE 3" SEC. 406.3 WITH A
 CLEANOUT OT 48" ABOVE FINISH FLOOR.
 5.SHOW DETAILS ON PLANS OF HANDICAP
 REQUIREMENTS AS LISTED BELOW;
 A.BATHROOM DIMENSIONS AND SHOW CLEAR
 FLOOR SPACE OF FIXTURES.
 B. SHOWER STALL REQUIRED TO MEET ALL
 REQUIREMENTS OF CHAPTER 11 SEC 11-4.21.1
 THRU 11-4.21.8.
 C.LACATORY SEC. 11-4.19.1 THRU
 11-4.19.6.
 D.TOILET SEC.11-4.16.1 THRU 11-4.16.6.
 E.GRAB BARS SEC. 11-4.17.6.
 F. DOOR SWING INTO CLEAR FLOOR SPACE
 SEC.11-4.17.5
 G.DRESSING ROOM SEC. 11-4.35.2 THRU
 11-4.35.5.
 6.MEANS OF THERMAL EXPANSION REQUIRED
 PLUMBING CODE SEC. 607.3. SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695