2006-06-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06060297 |
| ADD: 2916 S DIXIE HWY |
| CONT: TERRA CONSTRUCTION |
| TEL: (561)329-7676 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| --- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| FLORIDA BUILDING CODE/ 2004 |
| EXISTING BUILDING CODE/ 2004 |
| CLASSIFICATION OF WORK, |
| LEVEL 1,2 OR 3. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| IS THIS A CHANGE OF OCCUPANCY? |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER |
| SYSTEM IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| |
| OF THE BUILDING PERMIT. |
| |
| 2) SHEET A-1 OVERHEAD DOOR INFILL, PLANS |
| INDICATE THE USE OF 22 GA. STEEL STUDS. |
| THIS GAUGE STUDS ARE FOR INTERIOR USE |
| ONLY. STRUCTURAL GAUGE FRAMING IS 18 |
| GAUGE AND HEAVIER.ASTM C955 LOAD BEARING |
| STEEL STUDS, TABLE 22506.2. |
| |
| 3) SAME DETAIL INDICATES THE USE OF |
| PLYWOOD SHEATHING, SEE 2304.11.2.5 WOOD |
| SIDING. |
| CLEARANCE BETWEEN WOOD SIDING AND EARTH |
| ON THE EXTERIOR OF A BUILDING SHALL NOT |
| BE LESS THAN 6 INCHES (152 MM) EXCEPT |
| WHERE SIDING, SHEATHING AND WALL FRAMING |
| ARE OF NATURALLY DURABLE OR |
| PRESERVATIVE-TREATED WOOD . |
| 2304.9.5 FASTENERS IN PRESERVATIVE |
| TREATED AND FIRE-RETARDANT-TREATED WOOD |
| . FASTENERS FOR PRESERVATIVE TREATED AND |
| FIRE-RETARDANT-TREATED WOOD SHALL BE OF |
| HOT-DIPPED ZINC-COATED GALVANIZED STEEL, |
| STAINLESS STEEL, SILICON BRONZE OR |
| COPPER. FASTENINGS FOR WOOD FOUNDATIONS |
| SHALL BE AS REQUIRED IN AF&PA TECHNICAL |
| REPORT NO. 7. |
| |
| 4) OFFICE DOOR(A) MISSING 18" CLEARENCE |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 5) UNISEX RESTROOM DOOR:11-4.22.2 DOORS. |
| |
| (1)ALL DOORS TO ACCESSIBLE TOILET |
| ROOMS SHALL COMPLY WITH SECTION 11-4.13 |
| . DOORS SHALL NOT SWING INTO THE CLEAR |
| FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE.11-4.19.3 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE 30 INCHES BY 48 |
| INCHES (760 MM BY 1219 MM) COMPLYING |
| WITH SECTION 11-4.2.4 SHALL BE PROVIDED |
| IN FRONT OF A LAVATORY TO ALLOW FORWARD |
| APPROACH. SUCH CLEAR FLOOR SPACE SHALL |
| ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE |
| AND SHALL EXTEND A MAXIMUM OF 19 INCHES |
| (485 MM) UNDERNEATH THE LAVATORY (SEE |
| FIGURE 11-32 ). |
| |
| 6) SHOWER:11-4.21.7 CURBS. |
| IF PROVIDED, CURBS IN SHOWER STALLS 36 |
| INCHES BY 36 INCHES (915 MM BY 915 MM) |
| SHALL BE NO HIGHER THAN ? INCH (13 MM). |
| SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| INCHES (760 MM BY 1525 MM) MINIMUM SHALL |
| NOT HAVE CURBS. |
| |
| 7) EXISTING ENTRY DOORS APPEAR TO BE |
| APPROXIMATELY 2'-0" WIDE.ONE ENTRANCE |
| HAS STAIRS, DOES THE OTHER ENTRANCE HAVE |
| AN ACCESSIBLE ENTRANCE SINGLE DOOR 3'-0" |
| WIDE? |
| 11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |