Plan Review Notes For Permit 06060244 |
Permit Number |
06060244 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-06-30 00:00:00 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE 3-3/0 FEEDERS FROM THE UTILITY TO | | THE 600 AMP METER ARE INCORRECT. THERE | | IS 300 AMP OVERCURRENT PROTECTION IN THE | | MAIN GEAR. SEE 310.16. SHEET E2 DOES NOT | | CORRELATE WITH E1, WHICH SHOWS 250 | | ALUMINUM. | | | | 2} INDICATE THE PRIMARY AND SECONDARY | | FEEDER AND CONDUIT SIZES FROM THE | | DISCONNECTS TO THE 25KVA TRANSFORMER, | | RISER #1. | | | | 3} THE OCP FOR THE SECONDARY OF THE | | 25KVA TRANSFORMER IS NOT INDICATED, ONLY | | A 100 AMP DISCONNECT IS SHOWN, BUT THE | | OCP SIZE MUST COMPLY WITH 430.3(B). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | |
|