2006-06-20 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 600.6 DISCONNECTS.(A) LOCATION.
 (1) WITHIN SIGHT OF THE SIGN. THE
 DISCONNECTING MEANS SHALL BE WITHIN
 SIGHT OF THE SIGN OR OUTLINE LIGHTING
 SYSTEM THAT IT CONTROLS. WHERE THE
 DISCONNECTING MEANS IS OUT OF THE LINE
 OF SIGHT FROM ANY SECTION THAT MAY BE
 ENERGIZED, THE DISCONNECTING MEANS SHALL
 BE CAPABLE OF BEING LOCKED IN THE OPEN
 POSITION. SHOW THIS LOCATION ON THE
 DRAWING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW