Date |
Text |
2006-06-20 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} 600.6 DISCONNECTS.(A) LOCATION. | | (1) WITHIN SIGHT OF THE SIGN. THE | | DISCONNECTING MEANS SHALL BE WITHIN | | SIGHT OF THE SIGN OR OUTLINE LIGHTING | | SYSTEM THAT IT CONTROLS. WHERE THE | | DISCONNECTING MEANS IS OUT OF THE LINE | | OF SIGHT FROM ANY SECTION THAT MAY BE | | ENERGIZED, THE DISCONNECTING MEANS SHALL | | BE CAPABLE OF BEING LOCKED IN THE OPEN | | POSITION. SHOW THIS LOCATION ON THE | | DRAWING. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|