2006-06-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060067
 ADD: 400 N FLAGLER #804
 CONT: WILDES BUILDERS
 TEL: (772)260-8630
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1 INDICATES THIS TO BE A
 TYPE IA BUILDING SPRINKLERS REQUIRED.
 THIS BUILDING IS NOT FIRE SPRINKLERED.
  
 2) CODES TO BE DESIGNED AND REVIEWED BY
 ARE THE :
 2004 FLORIDA BUILDING CODE
 2004 EXISTING BUILDING CODE
 CLASSIFICATION OF WORK:
 LEVEL I
 LEVEL 2
  
 3) SOUND TRANSMITION:
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.