2006-06-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06060067 |
| ADD: 400 N FLAGLER #804 |
| CONT: WILDES BUILDERS |
| TEL: (772)260-8630 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A1 INDICATES THIS TO BE A |
| TYPE IA BUILDING SPRINKLERS REQUIRED. |
| THIS BUILDING IS NOT FIRE SPRINKLERED. |
| |
| 2) CODES TO BE DESIGNED AND REVIEWED BY |
| ARE THE : |
| 2004 FLORIDA BUILDING CODE |
| 2004 EXISTING BUILDING CODE |
| CLASSIFICATION OF WORK: |
| LEVEL I |
| LEVEL 2 |
| |
| 3) SOUND TRANSMITION: |
| 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING |
| ASSEMBLIES SEPARATING DWELLING UNITS |
| FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND |
| TRANSMISSION CLASS (STC) OF NOT LESS |
| THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| VENTILATING OR EXHAUST DUCTS SHALL BE |
| SEALED, LINED, INSULATED OR OTHERWISE |
| TREATED TO MAINTAIN THE REQUIRED |
| RATINGS. THIS REQUIREMENT SHALL NOT |
| APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING |
| UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT |
| LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| TESTED IN ACCORDANCE WITH ASTM E 492. |
| BUILDING PLAN REVIEW |