Date |
Text |
2006-09-07 00:00:00 | ** UNSAT 2ND REVIEW ** |
| |
| ** PLANS ARE NOW SUBMITTED FOR PERMIT. |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW. PLEASE |
| SEE NEW NOTE ADDED TO END OF NOTES. |
| |
| |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: NO, PLEASE SEE PLANS DO NOT |
| COMPLY AND INDICATE REQUIREMENTS FOR |
| CHAPTER 13 IN THE 2004 FBC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1,.1.2,.1.3 |
| PLEASE PROVIDE AN ACCEPTABLE METHOD, |
| SCHEDULING , DEVICES AND TIME LIMITS ON |
| DEVICES BEING USED. |
| ALL REQUIRED OVER RIDE DEVICE LOCATIONS |
| SHALL BE INDICATED ON PLANS. |
| PLEASE SEE ALL SEPARATE SPACES. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: NO, PLEASE SEE CONTINUOUS LOADS |
| ARE THAT OF WHICH ARE 3 OR MORE HRS AND |
| SHOULD BE INDICATED AT 125%. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE LOAD |
| CALCULATIONS WHICH MEET NEC 220. |
| 220.3,220.10,220.11,220.13 ETC |
| AND ALL CONTINUOUS LOADS AT 125%. |
| 215.5 |
| |
| 8) NOTE: OK. |
| |
| *** NEW NOTE ** |
| |
| 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO DESIGN PROFESSIONALS AND |
| REPEAT COMMENTS. THIS IS ONLYNOTICE |
| GIVEN AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |