Plan Review Notes For Permit 06051268 |
Permit Number |
06051268 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-09-07 00:00:00 | | | | | 1) SHEET A-3 HAS CONFLICTING | | INFORMATION.THE LIFE SAFETY SUMMARY | | INDICATES A SPRINKLER SYSTEM,HOWEVER, | | BELOW STATES A TYPE IV UNSPRINKLERED | | BUILDING. SO IS THERE A SPRINKLER SYSTEM | | IN THE BUILDING OR NOT? | | | | 2) THE OCCUPANT LOAD STATED ON SHEET A-3 | | IS INCORRECT. SEE TABLE 1004.1.2 FOR | | MORE INFORMATION AND MAKE THE | | ADJUSTMENTS ACCORDINGLY IN REFERENCE TO | | THE OCCUPANT LOAD. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | |
|