Plan Review Notes For Permit 06051268 |
Permit Number |
06051268 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-15 00:00:00 | FOR PLAN REVIEW ONLY | | | | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING | | CODES, LIFE SAFETY SHALL COMPLY WITH | | NFPA 101, 2003 EDITION. | | | | 2) AN EXIT SIGN IS SHOWN EXITING PERSONS | | THROUGH THE SHAMPOO/HAIR DRYING AREA. IT | | WOULD APPEAR THAT A BETTER LOCATION | | WOULD BE THE HALLWAY LEADING TO THE REAR | | EXIT. PLEASE SEE NFPA 101, SEC. 7.5.2.1. | | | | 3) PLEASE PROVIDE MAXIMUM TRAVEL | | DISTANCE INFORMATION TO LIFE SAFETY | | PLAN. | | | | 4) 2A 10B,C RATED FIRE EXTINGUISHER(S) | | REQUIRED MOUNTED AT DISTANCE NOT TO | | EXCEED 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|