2006-06-12 00:00:00 | ********** UNSAT ************* |
| |
| ** PLEASE SEE PLANS ARE ONLY SUBMITTED |
| FOR "PLAN REVIEW" AND HAVE NOT BEEN |
| SUBMITTED FOR PERMIT. |
| |
| 1) NOTE: PLEASE SEE PLANS SUBMITTED |
| SEEEM TO HAVE GOTTEN WET AND THE |
| SIGNATURE FOR THE ARCHITTECT ON BOTH |
| SETS HAVE BE DISTORTED. |
| FS481.221 |
| |
| 2) NOTE: PLEASE SEE FBC CHAPTER 13, |
| 13-415.1.ABC.1.1,.1.2,.1.3 |
| PLEASE PROVIDE AN ACCEPTABLE METHOD, |
| SCHEDULING , DEVICES AND TIME LIMITS ON |
| DEVICES BEING USED. |
| ALL REQUIRED OVER RIDE DEVICE LOCATIONS |
| SHALL BE INDICATED ON PLANS. |
| PLEASE SEE ALL SEPARATE SPACES. |
| |
| 3) NOTE: PLEASE CLARIFY FEEDERS TO |
| EXISTING PANEL. RISER SHOWS PARALLEL, |
| CONDUITS FOR A 400A SERVICE? |
| IS THE PANEL EXISTING 200A OR 400A? |
| IS THE EXISTING FEEDER ONE OR TWO 2" |
| CONDUITS? |
| 215.5 |
| |
| 4) NOTE: PLEASE SEE PLANS ARE INDICATING |
| DESIGN AND CODES UNDER THE 2001 FBC. |
| PLEASE KNOW, OCT 1ST, 2005 , THE FBC WAS |
| CHANGED TO THE 2004 FBC |
| PLEASE ADJUST PLANS AND CODES REFLECTED. |
| 215.5 |
| |
| 5) NOTE: PLEASE SEE MANY CIRCUITS ON |
| PANEL SCHEDULE ARE SHOWN AS "EXISTING"?? |
| HOW IS THIS POSSIBLE WHEN THIS IS A NEW |
| BUILD OUT OF AN EXISTING SPACE?? |
| PLEASE CORRLEATE PLANS. |
| |
| 6) NOTE: PLEASE SEE 408.4, PANEL |
| SCHEDULE SHALL INDICATE ALL CIRCUITS |
| SPECIFIC TO ROOMS AND AREAS. IE; BATH |
| LTS, OFFICE LTS, OFFICE RECEPTS ETC. |
| 215.5 |
| |
| 7) NOTE: PLEASE PROVIDE LOAD |
| CALCULATIONS WHICH MEET NEC 220. |
| 220.3,220.10,220.11,220.13 ETC |
| AND ALL CONTINUOUS LOADS AT 125%. |
| 215.5 |
| |
| 8) NOTE: PLEASE COMPLETE ALL CIRCUITS ON |
| PLANS AND CORRELATE WITH THE PANEL |
| SCHEDULE. |
| PLEASE SEE 700.12E FOR CIRCUITING OF EM |
| /EXT LTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |