Plan Review Notes For Permit 06051263 |
Permit Number |
06051263 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-03 00:00:00 | | | DENIED | | | | 1) SCOPE OF WORK HARD TO DISCERN. IS NEW | | LAUNDRY AREA ONLY ACCESSABLE FROM | | OUTSIDE? DOES NEW INTERIOR FRAMED WALLS | | HAVE A WINDOW IN THEM? IS EXISTING DOOR | | OPENING A DOUBLE DOOR? A DRAWING WITH | | MORE CLARITY IS REQUIRED TO ACCOMPLISH | | REQUIRED PLAN REVIEW | | | | 2) DETAIL SHOWS DOOR AND WINDOW TOGETHER | | IS POST BETWEEN STRUCTURAL? WHAT IS IT'S | | MAKE UP (DOUBLE 2X ?)AND HOW IS IT | | ATTACHED TO THE BEAM AND FLOOR SYSTEM | | | | 3) PRODUCT APPROVALS ARE REQUIRED FOR | | DOORS AND WINDOWS PER 9B-72 FAC | | | | 4)A DETAIL IS REQUIRED ON PATCH FOR | | EXISTING WINDOW OPENING TO BE FILLED | | | | 5) IS INTERIOR POST STRUCTURAL? IF SO | | WHAT FRAMING WILL REPLACE IT? | | | | 6) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO A | | PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|