2006-06-20 00:00:00 | ********* UNSAT *************** |
| |
| 1A) NOTE: PLEASE SEE PERMIT APPLICATION |
| IS SOMEWHAT CONFUSING. APPL MENTIONS |
| "COOLER AND FREEZER" INSTALL, YET IT |
| ALSO MENTIONS COOLER PERMIT UNDER |
| SEPARATE PERMIT?? |
| PLEASE SEE PLANS ALSO MENTION COOLER AND |
| FREEZER IS "NOT" INCLUDED?? |
| PLEASE SEE COMMENTS FROM BUILDING REVIEW |
| AS SCOPE OF WORK DOES NOT SEEM TO ALLOW |
| A PERRMIT UNDER THE "U" LICENSE. |
| THE PRIME SOURCE OF WORK IS MECHANICAL |
| AND IT SEEMS THIS SHOULD BE THE PRIME |
| FROM THE MECHANICAL CONT. |
| |
| ** PLEASE KNOW, IN EITHER CASE THE |
| COMPLETE VALUE FOR SCOPE PF WORK SHALL |
| INCLUDE ALL LABOR AND |
| MATERIALS,INCLUSIVE OF ANY MATERIALS OR |
| EQUIPMENT WHICH MAY BE OWNER SUPPLIED. |
| PLEASE SEE VALUE OF $15K IS WAY LOW FOR |
| SCOPE ON PLANS. |
| FBC 108.3 ADMIN SECT. |
| |
| 1B) NOTE: PLANS INDICATE THESE WERE TWO |
| TENANT SPACES WHICH ARE NOW BECOMING |
| ONE, PLEASE SEE BUILDING REVIEW NOTES |
| FOR STRUCTURAL SCOPE OF WORK NOT BEING |
| SHOWN. |
| |
| 2) NOTE: PLEASE SEE RISER FEEDERS DO NOT |
| MEET MIN SIZES AS REQUIRED FOR THE NEW |
| 400A SERVICE BEING PROVIDED. |
| PLEASE ALSO INCLUDE CONDUCTORS FROM |
| GUTTER TO METER AND METER TO MAIN. |
| PLEASE SEE 250.6,250.24B,310.16, 240.4, |
| ETC |
| 215.5 |
| |
| 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 4) NOTE: PLEASE INDICATE OF TOTAL LOAD |
| SHOWN ON SERVICE CALC IS INCLUDING NEW |
| LOADS? |
| PLEASE ALSO INDICATE THE CONTINOUS LOADS |
| AND ANY LARGEST MOTOR LOADS AT 125%. |
| 215.3,230.42 ETC. |
| |
| 5) NOTE: PLEASE SUBMIT ENERGY CODE |
| COMPLIANCE FORMS FOR EQUIPMENT AND |
| SPACE.THESE SAHLL BE SIGNED , DATED AND |
| SEALED BY THE REPSONSIBLE ENGINEER OF |
| RECORD. |
| FBC 2004 CHAPTER 13 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |