2006-06-20 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06051259 |
| ADD: 5407 N HAVERHILL RD |
| CONT: GABCO |
| TEL: (561)644-1434 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| --- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) AS STATED BY OTHER REVIEWERS, THE |
| LICENSE HOLDER GABCO REMODELING IS A |
| GENERAL CONTRACTOR AND NOT LICENSED TO |
| INSTALL COOLERS AND FREEZERS. THE PLANS |
| ONLY INDICATE COOLER AND FREEZERS NO |
| OTHER WORK IS SHOWN. |
| |
| 2603.4.1.2 COOLER AND FREEZER WALLS. |
| FOAM PLASTIC INSTALLED IN A MAXIMUM |
| THICKNESS OF 10 INCHES (254 MM) IN |
| COOLER AND FREEZER WALLS SHALL: |
| 1.HAVE A FLAME SPREAD INDEX OF 25 |
| OR LESS AND A SMOKE-DEVELOPED INDEX OF |
| NOT MORE THAN 450, WHERE TESTED IN A |
| MINIMUM 4 INCH (102 MM) THICKNESS. |
| 2.HAVE FLASH IGNITION AND |
| SELF-IGNITION TEMPERATURES OF NOT LESS |
| THAN 600?F AND 800?F (316?C AND 427?C), |
| RESPECTIVELY. |
| 3.HAVE A COVERING OF NOT LESS THAN |
| 0.032-INCH (0.8 MM) ALUMINUM OR |
| CORROSION-RESISTANT STEEL HAVING A BASE |
| METAL THICKNESS NOT LESS THAN 0.0160 |
| INCH (0.4 MM) AT ANY POINT. |
| 4.BE PROTECTED BY AN AUTOMATIC |
| SPRINKLER SYSTEM. WHERE THE COOLER OR |
| FREEZER IS WITHIN A BUILDING, BOTH THE |
| COOLER OR FREEZER AND THAT PART OF THE |
| BUILDING IN WHICH IT IS LOCATED SHALL BE |
| SPRINKLERED. |
| |
| 2603.4.1.3 WALK-IN COOLERS. |
| IN NONSPRINKLERED BUILDINGS, FOAM |
| PLASTIC HAVING A THICKNESS THAT DOES NOT |
| EXCEED 4 INCHES (102 MM) AND A MAXIMUM |
| FLAME SPREAD INDEX OF 75 IS PERMITTED IN |
| WALK-IN COOLERS OR FREEZER UNITS WHERE |
| THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| 400 SQUARE FEET (37 M 2 ) AND THE FOAM |
| PLASTIC IS COVERED BY A METAL FACING NOT |
| LESS THAN 0.032-INCH-THICK (0.81 MM) |
| ALUMINUM OR CORROSION-RESISTANT STEEL |
| HAVING A MINIMUM BASE METAL THICKNESS OF |
| 0.016 INCH (0.41 MM). A THICKNESS OF UP |
| TO 10 INCHES IS PERMITTED WHERE |
| PROTECTED BY A THERMAL BARRIER. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |