Plan Review Notes
Plan Review Notes For Permit 06051259
Permit Number 06051259
Review Stop B
Sequence Number 1
Notes
Date Text
2006-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051259
 ADD: 5407 N HAVERHILL RD
 CONT: GABCO
 TEL: (561)644-1434
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) AS STATED BY OTHER REVIEWERS, THE
 LICENSE HOLDER GABCO REMODELING IS A
 GENERAL CONTRACTOR AND NOT LICENSED TO
 INSTALL COOLERS AND FREEZERS. THE PLANS
 ONLY INDICATE COOLER AND FREEZERS NO
 OTHER WORK IS SHOWN.
  
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM
 THICKNESS OF 10 INCHES (254 MM) IN
 COOLER AND FREEZER WALLS SHALL:
 1.HAVE A FLAME SPREAD INDEX OF 25
 OR LESS AND A SMOKE-DEVELOPED INDEX OF
 NOT MORE THAN 450, WHERE TESTED IN A
 MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND
 SELF-IGNITION TEMPERATURES OF NOT LESS
 THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN
 0.032-INCH (0.8 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM
 PLASTIC HAVING A THICKNESS THAT DOES NOT
 EXCEED 4 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE
 THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL
 HAVING A MINIMUM BASE METAL THICKNESS OF
 0.016 INCH (0.41 MM). A THICKNESS OF UP
 TO 10 INCHES IS PERMITTED WHERE
 PROTECTED BY A THERMAL BARRIER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  