2006-06-02 00:00:00 | *** DENIED *** |
| 1) PLEASE SUBMIT ENERGY CALCULATIONS |
| (SHORT FORM) PER 2004 FBC 13-600. |
| |
| 2) PLEASE STATE HOW MANY SYSTEMS ARE |
| BEING INSTALLED ON MECHANICAL PLANS. |
| |
| 3) SHOW SENSIBLE BTU'S AND TOTAL BTU'S |
| OF EQUIPMENT ON MECHANICAL PLANS. |
| |
| 4) SHOW EQUIPMENT SEER ON MECHANICAL |
| PLANS. |
| |
| 5) SHOW ALL GRILL SIZES WITH CFM'S ON |
| MECH. PLANS. |
| |
| 6) SHOW TRUNK LINE SIZE ON PLANS. |
| |
| 7) SHOW ON PLANS HOW AIR HANDLER UNITS |
| ARE GETTING RETURN AIR, IF GRILLS SHOW |
| SIZE. |
| |
| 8) PROVIED RETURN AIR TO BEDROOMS, SEE |
| NOTE #11. |
| |
| 9) CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 |
| |
| 10) ALL INFORMATION/ DRAWINGS/ |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| SECTION 104.2.1 |
| |
| 11) BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |