2006-10-18 11:59:09REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) 9" RETURN AIR DUCT FROM 24X12 GRILL TO AHU IS TO
 SMALL FOR 1000 CFM'S, PLEASE CORRECT.
  
 2) 9" RETURN AIR DUCTS TO BEDROOMS MAY BE TO SMALL IF
 THEY ARE TRANSFER DUCTS, CORRECT IF NEEDED.
  
 MECHANICAL PLAN REVIEW BY;