Plan Review Notes For Permit 06051226 |
Permit Number |
06051226 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-10-18 11:59:09 | REVISION TO MECHANICAL PLANS | | *** DENIED *** | | 1) 9" RETURN AIR DUCT FROM 24X12 GRILL TO AHU IS TO | | SMALL FOR 1000 CFM'S, PLEASE CORRECT. | | | | 2) 9" RETURN AIR DUCTS TO BEDROOMS MAY BE TO SMALL IF | | THEY ARE TRANSFER DUCTS, CORRECT IF NEEDED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|