Date |
Text |
2006-07-26 00:00:00 | ******** UNSAT2ND REVIEW ********* |
| |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED ALONG WITH NEW COMMENTS. |
| |
| 1) NOTE: NO, NOT DONE. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: NO, NOT DONE. NEED TO SHOW TO |
| VERIFY IF THESE ARE SIZED CORRECTLY. |
| RISER ONLY SHWOS FEEDERS FROM MAIN TO |
| SUB PANEL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING SEC'S PER |
| 310.15B6,310.16,240.4,240.6,215.5 |
| |
| 4) NOTE: OK. HOWVER SEE ABOVE. |
| |
| 5) NOTE: OK. |
| |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK, HOWEVER SEE NEW ARC FAULT |
| NOTE. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE:OK. |
| |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE:NO, NOT DONE, THIS IS STILL |
| REQUIRED FOR ALL TRADES AND FOR ALL |
| SHEETS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING REQUIRED |
| LICENSE INFORMATION ON TITLE BLOCKS OF |
| SAID PLANS. |
| PLEASE SEE FAC 61G1-16.004, FS481.219. |
| PLEASE KNOW, THIS IS REQUIRED OF ALL |
| SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| COMMENTS IS MADEBY OTHER TRADES. |
| |
| 13) NOTE:OK. |
| |
| 14) NOTE: OK. |
| |
| 15) NOTE: OK. |
| |
| ** NEW NOTES ** |
| |
| 16) NOTE: PLEASE MISSING COLD WATER PIPE |
| FOR GE SYSTEM. |
| 250.50. |
| |
| 17) NOTE: PLEASE SEE ARC FAULT NOTE #3 |
| WAS ADDED TO PLANS AND PANEL SCHEDULE, |
| HOWEVER PLEASE SEE NOT ALL REQUIRED |
| CIRCUITS SHOW THE #3 NOTE. |
| 210.12B |
| |
| 18) NOTE: PLEASE SEE ATTACHED SHEET WITH |
| RESPECT TO DESIGN PROFESSIONALS AND |
| REPEAT CODE COMPLIANT COMMENTS. |
| FS 553.80(2)(B). |
| |
| 19) NOTE: IMPORTANT** |
| BEFORE RESUBMITTING PLANS, PLEASE |
| COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |