Plan Review Notes
Plan Review Notes For Permit 06051226
Permit Number 06051226
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-14 00:00:00******** UNSAT **********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3) NOTE: PLEASE SEE MISSING SEC'S PER
 310.15B6,310.16,240.4,240.6,215.5
  
 4) NOTE: PLEASE SEE FEEDERS ARE NOT
 LAREGE ENOUGH FOR 200A SERVICE AS SHOWN
 FROM MAIN TO PANEL.
 310.16, 240.4
  
 5) NOTE: PLEASE CORRELATE ALL CIRCUTING
 ON PANEL SCHEDULE WITH LOADS ON LOAD
 CALCS.
 PLEASE SEE RANGE, WATER HEATER, DRYER
 ETC.
 215.5
  
 6) NOTE: PLEASE SEE WH IS SHOWNAS 1-15A
 BRKR WITH 4500VA LOAD??
 240.4,310.16,240.6
  
 7) NOTE: PLEASE SEE MANY CIRUITS NOTED
 AS ARC FAULT WHICH ARE IN QUESTION??
 WATER HEATER , DRYER ETC??
 PLEASE EXPLAIN.
 215.5
  
 8) NOTE: PLEASE SHOW THE LOCATION ON
 PLAN FOR SERVICE LOCATION.
 215.5
  
 9) NOTE: PLEASE SEE MIN CLEARENCES PER
 110.26 FOR AHU AND WH.
  
 10) NOTE: PLEASE SEE MIN OCP FOR STOVE
 SHOUDL CORRELATE WITH THE KW RATING.
 PLEASE SEE LOAD EXCEEDS RATING OF THE
 OCP/BREAKER.
 240.4,310.16 ETC
 215.5
  
 11) NOTE: PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODE IN EFFECT.
 2002 NEC.
 FBC ADMIN SECTION AS AOPTED BY THE CITY
 OF WEST PALM BEACH 106.2.1
  
 12) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS OF
 SAID PLANS.
 PLEASE SEE FAC 61G1-16.004, FS481.219.
 PLEASE KNOW, THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENTS IS MADEBY OTHER TRADES.
  
 13) NOTE: PLEASE SEE MIN GEC SHALL BE
 SIZED PER 250.66.
  
 14) NOTE: PLEASE SEE PANEL SCHEDULE
 SHOWS TWO BATH RECEPT CIRCUITS??
 PLEASE SEE BOTH ARE SHOWN AS 20A #12,
 ONE FOR LT AND ONE FOR RECEPT.
  
 15) NOTE: PLEASE SEE MISSING
 WASHER/LAUNDRY CIRCUIT PER 210.11C1,
 220.16SHALL BE A MIN OF 1500VA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  