2006-06-14 00:00:00 | ******** UNSAT ********** |
| |
| |
| 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2) NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 3) NOTE: PLEASE SEE MISSING SEC'S PER |
| 310.15B6,310.16,240.4,240.6,215.5 |
| |
| 4) NOTE: PLEASE SEE FEEDERS ARE NOT |
| LAREGE ENOUGH FOR 200A SERVICE AS SHOWN |
| FROM MAIN TO PANEL. |
| 310.16, 240.4 |
| |
| 5) NOTE: PLEASE CORRELATE ALL CIRCUTING |
| ON PANEL SCHEDULE WITH LOADS ON LOAD |
| CALCS. |
| PLEASE SEE RANGE, WATER HEATER, DRYER |
| ETC. |
| 215.5 |
| |
| 6) NOTE: PLEASE SEE WH IS SHOWNAS 1-15A |
| BRKR WITH 4500VA LOAD?? |
| 240.4,310.16,240.6 |
| |
| 7) NOTE: PLEASE SEE MANY CIRUITS NOTED |
| AS ARC FAULT WHICH ARE IN QUESTION?? |
| WATER HEATER , DRYER ETC?? |
| PLEASE EXPLAIN. |
| 215.5 |
| |
| 8) NOTE: PLEASE SHOW THE LOCATION ON |
| PLAN FOR SERVICE LOCATION. |
| 215.5 |
| |
| 9) NOTE: PLEASE SEE MIN CLEARENCES PER |
| 110.26 FOR AHU AND WH. |
| |
| 10) NOTE: PLEASE SEE MIN OCP FOR STOVE |
| SHOUDL CORRELATE WITH THE KW RATING. |
| PLEASE SEE LOAD EXCEEDS RATING OF THE |
| OCP/BREAKER. |
| 240.4,310.16 ETC |
| 215.5 |
| |
| 11) NOTE: PLEASE SEE PLANS SHALL |
| INDICATE THE CURRENT CODE IN EFFECT. |
| 2002 NEC. |
| FBC ADMIN SECTION AS AOPTED BY THE CITY |
| OF WEST PALM BEACH 106.2.1 |
| |
| 12) NOTE: PLEASE SEE MISSING REQUIRED |
| LICENSE INFORMATION ON TITLE BLOCKS OF |
| SAID PLANS. |
| PLEASE SEE FAC 61G1-16.004, FS481.219. |
| PLEASE KNOW, THIS IS REQUIRED OF ALL |
| SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| COMMENTS IS MADEBY OTHER TRADES. |
| |
| 13) NOTE: PLEASE SEE MIN GEC SHALL BE |
| SIZED PER 250.66. |
| |
| 14) NOTE: PLEASE SEE PANEL SCHEDULE |
| SHOWS TWO BATH RECEPT CIRCUITS?? |
| PLEASE SEE BOTH ARE SHOWN AS 20A #12, |
| ONE FOR LT AND ONE FOR RECEPT. |
| |
| 15) NOTE: PLEASE SEE MISSING |
| WASHER/LAUNDRY CIRCUIT PER 210.11C1, |
| 220.16SHALL BE A MIN OF 1500VA |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |