Date |
Text |
2006-11-28 19:16:47 | **** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE MISSING LIGHTING CONTROL OVER RIDE |
| DEVICE IN ROOM 1205. |
| 13-415.1.ABC.1.2 PLEASE ADJUST ON E-3 |
| |
| 2) NOTE: PLEASE SEE MISSING ONLY THE CANDELA LEVELS |
| REQUIRED PER FBC 2004 11-4.28.1 AND 11-4.28.3(4) IS |
| PERMITTED. THIS IS 75 MIN. PLEASE ADJUST NOTE ON E-5 |
| |
| 3) NOTE: PLEASE SEE COMPLETE UPS BACK UP SYSTEM NOT IN |
| SCOPE OR PERMITTED UNDER THIS PERMIT IS NOW BEING SHOWN |
| ON PLANS. THE INFORMATION FOR ALL EQUIPMENT AND VALUE |
| FOR SCOPE OF WORK WAS PREVIOUSLY REQUESTED ON REVIEWS |
| DATING BACK BEFORE PERMITTING AND THE DESIGNER OF |
| RECORD REMOVED FROM PROJECT STATING THIS SCOPE OF WORK |
| WOULD NOT BE DONE. PLEASE SEE NOW PLANS INDICATE THIS. |
| PLEASE SUBMIT ALL THE PREVIOUSLY REQUESTED INFORMATION |
| FOR SAID SYSTEM UNDER A SEPARATE PERMIT INCLUDING |
| PERMIT APPLICATION, SIGNED DATED AND SEALED PLANS, |
| ALONG WITH ALL MANUFACTURES SPEC/CUT SHEETS FOR ALL UPS |
| EQUIPMENT. |
| PLEASE KNOW THE VALUE FOR THIS SCOPE OF WORK SHALL BE |
| BASED ON ALL LABOR AND MATERIALS WHETHER OR NOT |
| EQUIPMENT IS OWNER SUPPLIED. PLEASE KNOW, ONCE A PERMIT |
| FOR THIS SCOPE OF WORK IS ISSUED, THEN A REVISION |
| INCLUDING THIS SCOPE OF WORK ON THE MAIN BUILDING |
| PERMIT MAY BE SUBMITTED, HOWEVER NOTING THIS WORK UNDER |
| A SEPARATE PERMIT. |
| |
| ** PLEASE SEE SHEETS E-3- E-5 WHICH WERE STAMPED AND |
| WERE BEING REDLINED WERE STAMPED "VOID" UNTIL SCOPE |
| ABOVE IS ADDRESSED. |
| THIS WORK WAS TAKEN OUT OF THE ORIGINAL PLANS. |
| |
| FBC 106.1.2, 106.3.5.1.2 |
| NEC 110.3, 90.7, 645.11 ETC. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF |
| NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER |
| WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE OR REVIEWER. |
| |