Plan Review Notes
Plan Review Notes For Permit 06051212
Permit Number 06051212
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-19 08:59:52********* PROVSIO ********
  
  
 1) NOTE: PLEASE SEE CONFERENCE ROOMS 1201 AND 1203 DO
 NOT SEEM TO CONTAIN OVER-RIDE DEVICES FOR LIGHTING
 CONTROLS. PLEASE SEE LIGHTING RELAY SCHEDULE ALSO DOES
 NOT SEEM TO INDICATE THESE CIRCUITS.
  
 2) NOTE: PLEASE SEE REDLINE E-5 AS COMMENT FOR MINIMUM
 LEVELS FOR HORN/STROBES IS NOT STAED. THIS HAS NOW
 BECOME PART OF THE ELECTRICAL PLAN REVIEW PROCESS.
 PLEASE SEE FBC 200411-4.28., 11-4.28.2, FOR MIN
 ADUDIBLE LEVELS AND 11-4.28.3(4) FOR MIN LIGHTING
 CANDELA.
  
 ** PLEASE BE SURE TO SHOW THESE AND AND INCLUDE ON
 PLANS. SUBMIT REVISED PLANS ALONG WITH ANY OTHER
 REVISIONS BEFORE ANY ROUGHT ELECTRICLA INSPECTION.
 REVISED STAMPED PLANS MUST BE ON SITE FOR ELECTRICLA
 INSPECTOR.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PAN REVIEW
 561-805-6717
2006-10-18 21:05:33IN ELECTRICAL FOR REVIEW, REVIEW IN PROGRESS