Plan Review Notes
Plan Review Notes For Permit 06051212
Permit Number 06051212
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-20 00:00:00**** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW AND SOME NEW NOTES ARE IN NEED OF
 ADDRESSING.
  
 1) NOTE: OK, AS SCOPE ON PLANS HAS
 DECREASED.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE THE E-SHEETS
 WERE NOTE DATED WHEN SIGNED BY THE
 ENGINEER. PLEASE MAKE SURE ALL THE NEW
 REVISED SHEETS ARE DATED WHEN SIGNING
 AND SEALING SADI DOCUMENTS. FS 471.025,
 FAC 61G15-23.002.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT PLANS ARE NOTE DATED BY
 THE ARCHITECT OR ENGINEER AS REQUIRED
 UNDER FS 481.221, 471.025.
  
 5) NOTE: OK/NO, PLEASE SEE NEW ENERGY
 CALCUALTIONS WERE SUBMITTED HOWEVER
 THESE DO NOT CONTAIN A RAISED SEAL AS
 REQUIRED. PLEASE SEE A "RUBBER STAMP" IS
 PLACE IN LEIU OF THE REQUIRED RAISED
 SEASL. FAC 61G15-23.001
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CORRECTED ENERGY
 CODE CALCULATIONS SHAL BE DESIGNED UNDER
 FBC 2004.
 PLEASE SEE THEY CURRENTY INDICATE THE
 2001 ICC.
 PLEASE BE SURE THEY ARE SIGNED , DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1,
 13-415.2.ABC.1
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK, SEE NEW NOTES.
  
 11) NOTE: OK.
  
 12) NOTE: NO, THIS IS UNCLEAR STILL AS
 RISER NOW SHOWS A MAIN AHEAD OF THE FPL
 METER. PLEASE KNOW, PER FPL GUIDLINES
 FOR SERVICES, A MAIN IS REQUIRED ON THE
 LOAD SIDE OF METER. PLEASE KNOW, IF
 INDEED THIS IS INSTALLED AS SHOWN PLEASE
 BE SURE TO INDICATE A "FLOATING
 NEUTRAL".
 PLEASE SEE NEW NOTES FOR LOAD
 CALCUALTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY RISER, IS THE
 "EXISTING TENANT" BEING SHOWN ON THE
 RISER ANOTHER TENANT SPACE OR IS THIS
 THE EXISTING TENANT RISER FOR THIS
 SPACE?
 AS SHOWN, THERE SEEMS TO BE AN EXISTING
 TENANT AND THIS NEW BUILD OUT IS NOTW
 TAPPING THE EXISTING METER AS SHOWN??
 THIS IS NOT CLEAR AT THIS TIME.
 215.5
  
 13) NOTE: NO/UNCLEAR SEE NOTE ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE EXISTING , OR
 NEW METER SIZE AND WHERE THE
 DISCONNECTING MEANS FOR SERVICE IS
 LOCATED AND THE OCP AND SIZE OF TENANT
 SERVICE DISCONNECT.
 CURRENTLY THIS IS NOT SHOWING ANY MAIN,
 AND A 42 CIRCUIT MLO FOR TENANTS
 DISCONNECTING MEANS.
 215.5,240.4,310.16,230.70 ETC
  
 14) NOTE: NO, PLEASE SEE ATTACHMENT ONLY
 BEING NTOED FOR THE 45K UNIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE TH ACTUAL
 ATTACHMENT FOR THE GROUNDING ELECTRODE
 OF THE NEW SEPARATELY DERIVED
 TRANSFORMERS.
 250.66, 250.30
 THE NOTE ON PLANS NEEDS TO BE SHOWN.
  
 15) NOTE: OK. SEE NEW NOTES.
  
  
 16) NOTE: OK.
  
  
 ** NEW NOTES**
  
 17) NOTE: PLEASE SSUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE EXISTING 200A MIAN
 AND METER BEING SHOWN. (LOADS FOR "H",
 "L" AND "CR.
 220,
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE IT ROOM DOES NOT
 INDICATE THE TRANSFORMER ON ROOM LAYOUT?
 PLEASE SEE RISER AND NOTE MENTIONS THIS
 IS A FLR MOUNTED UNIT.
 PLEASE SEE 110.26
  
 19) NOTE: PLEASE SEE PANEL "CP" IS BEING
 SHOWN AS 125A RATED AND FED FROM "RP"
 WHICH IS 150A MCB AND FEED-THRU LUGS.
 THEN PANEL "CP" WOULD ALSO BE REQUIRED
 TO BE 150A RATED, OR IF USING A TAPPED
 CONDUCTOR RULE, TERMINATE IN OCP WHICH
 LIMITS THE LOAD.
 240.21, 408.16, 240.3
 THIS WAS SHOWN AS THE SAME ON PREVIOUS
 PLANS, HOWEVER WAS NOT COMMENTED ON.
  
 20) NOTE: PLEASE SEE THE FOLLOWING AS
 THE FIRST COMMENT FROM BUILDING REVIEWER
 REQUESTED ALL OLD/VOIDED SHEETS BE
 REMOVED, YET PLEASE SEE ALL OLD
 ELECTRICAL SHEETS WERE LEFT IN SETS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  