Plan Review Notes For Permit 06051212 |
Permit Number |
06051212 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-22 00:00:00 | ***DENIED*** | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS | | REGARDING FAC REQUIREMENTS FOR TITLE | | BLOCKS. | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. PLEASE NOTE THAT THE WORD | | CHANGE FROM 'CERTIFICATE' TO 'LICENSE' | | IS REQUIRED FOR ANY SEALED DRAWINGS | | SUBMITTED FOR THESE SYSTEMS. | | | | 3) FOR SPRINKLER REMODEL, NFPA 13, 2002 | | EDITION SHALL BE REFERENCED. | | | | 4) CONSTRUCTION, ALTERATION AND | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | 5) PLANS ILLUSTRATE ELECTRIC LOCKS AND | | CARD READERS. WHAT IMPACT WILL THIS | | ARRANGEMENT HAVE ON REQUIRED EXITING? | | DOORS SHALL COMPLY WITH NFPA 101, 2003 | | EDITION SEC. 7.2.1.5. | | | | 6) 2A-10B,C RATED FIRE EXTINGUISHERS | | SHALL BE MOUNTED AT DISTANCES NOT TO | | EXCEED 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|