Plan Review Notes
Plan Review Notes For Permit 06051212
Permit Number 06051212
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 REGARDING FAC REQUIREMENTS FOR TITLE
 BLOCKS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL. PLEASE NOTE THAT THE WORD
 CHANGE FROM 'CERTIFICATE' TO 'LICENSE'
 IS REQUIRED FOR ANY SEALED DRAWINGS
 SUBMITTED FOR THESE SYSTEMS.
  
 3) FOR SPRINKLER REMODEL, NFPA 13, 2002
 EDITION SHALL BE REFERENCED.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 5) PLANS ILLUSTRATE ELECTRIC LOCKS AND
 CARD READERS. WHAT IMPACT WILL THIS
 ARRANGEMENT HAVE ON REQUIRED EXITING?
 DOORS SHALL COMPLY WITH NFPA 101, 2003
 EDITION SEC. 7.2.1.5.
  
 6) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCES NOT TO
 EXCEED 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722