2006-06-19 00:00:00 | IN ELEC FOR REVIEW. |
| ********** UNSAT *********** |
| |
| 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF |
| WORK SHALL INCLUDE ALL MATERIALS AND |
| LABOR (EVEN IF ANY EQUIPMENT IS OWNER |
| SUPPLIED). |
| PLEASE SEE UPGRADE , AND SPECIALLY |
| DESIGNED LIGHTING CONTROL SYSTEMS ETC |
| SHALL ALOS BE INCLUDED IN VALUE IF SHOWN |
| ON PLANS. |
| ALL PERMANANTLY INSTALLED SYSTEMS. |
| FBC ADMINISTRATIVE SECTION 108.3 AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION |
| REQUIRED ON ALL TITLE BLOCKS ON PLANS. |
| PLEASE SEE MISSING ARCHITECTURAL FIRM |
| CERTIFICATE OF AUTHORIZATION #. |
| PLEASE SEE MISSING ENGINEERING FIRM CA#. |
| PLEASE SEE MISSING THE PRINTED NAME AND |
| PRINTED LICENSE # OF SAID ARCHITECT. |
| PLEASE SEE ALL OF THE ABOVE IS REQUIRED |
| PER FLORIDA ADMINISTRATIVE CODES |
| 61G1-16.004, 61G15-23.002, FLORIDA |
| STATUES 481.219, AND FS471.023 |
| ** THIS IS REQUIRED OF ALL TRADES AND |
| FOR ALL SHEET WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.001 WHICH |
| PASSED A RULING IN FEB 04 WHICH REQUIRED |
| ALL ENGINEER'S SEALS TO CONTAIN THE |
| WORDING OF "LICENSE" IN SEAL. PLEASE SEE |
| THAT ALL SEALS WITH THE WORDING OF |
| "CERTIFICATE" ARE NOT LONGER ACCEPTABLE. |
| |
| 4) NOTE: PLEASE SEE THAT PLANS ARE NOT |
| DATED BY THE ARCHITECT OR ENGINEER AS |
| REQUIRED UNDER FS 481.221 AND 471.025 |
| |
| 5) NOTE: PLEASE SEE CORRECTED ENERGY |
| CODE CALCULATIONS SHAL BE DESIGNED UNDER |
| FBC 2004. |
| PLEASE SEE THEY CURRENTY INDICATE THE |
| 2001 ICC. |
| PLEASE BE SURE THEY ARE SIGNED , DATED |
| AND SEALED BY THE ENGINEER OF RECORD. |
| PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1, |
| 13-415.2.ABC.1 |
| |
| 6) NOTE: PLEASE BE SURE PLANS INCLUDIGN |
| ELECTRICAL REFLECT THE CURRNT CODE IN |
| EFFECT FOR DESIGN. |
| PLEASE SEE PLANS SHOULD INCLUDE THE |
| FOLLOWING AT A MIN. |
| 2002 NFPA-70, (2005 SHOWN), 2003 |
| NFPA-101, NFPA-72 2002, NFPA-75 2003. |
| |
| 7) NOTE: PLEASE CLARIFY LIGHTING |
| CONTROLS FOR ALL ROOMS AS SOME COULD NOT |
| BE LOCATED FOR THE OVER RIDE DEVICES AS |
| REQUIRED. |
| FBC 13-415.1.ABC.1.1, .1.2 ETC. |
| 1205,1202,1203,1201 |
| ** PLEASE SPECIFY TIME LIMITS ON |
| DEVICES. CAN BE A "TYPICAL" NOT FOR NO |
| MORE THAN 30 MINS FOR OS TYOE DEVICES |
| AND 4HRS FOR TIMED TYPE DEVICES. |
| ** PLEASE SEE A OSZ2 DEVICE IS SHOWN ON |
| PLANS, HOWEVER COULD NOT LOCATED THIS ON |
| LEGEND? |
| |
| 8) NOTE:PLEASE SEE FIRE REVIEW |
| COMMENTS AS TYPE OF "ELEC LOCK" FOR |
| ACCESS CONTROLS NEED TO BE CLARIFIED. |
| PLEASE SEE THAT IN THE EVENT OF POWER |
| FAILURE, EGREES SHALL NOT IMPEDED. |
| |
| 9) NOTE: PLEASE SEE THAT PLANS CLEARLY |
| INDICATE THE FLR AND SUITE NUMBER IN |
| TITLE BLOCK. |
| FAC 61G1-16.004 |
| |
| 10) NOTE: PLEASE KNOW, AN "ALTERNATE" |
| SYSTEM IS BEING SHOWN FOR THE IT ROOM. |
| PLEASE KNOW, IF THIS SYSTEM IS BEING |
| PROPOSED THEN IT SHOULD BE ON PLANS, IF |
| NOT THIS SHOULD BE REMOVED. IF THIS |
| SYSTEM IS GOING TO BE INSTALLED, PLEASE |
| PROVIDE ALL MANUFACTURES SPCES/CUT |
| SHEETS INDICATE A LISTING FROM A NRTL. |
| 215.5 |
| |
| 11) NOTE: PLEASE CLARIFY ROOM BEING |
| INDICATE AS AN "IT" ROOM ON PLANS WHICH |
| SHALL MEET NFPA-75 AND NEC 645. |
| PLEASE CLARIFY IF THERE IS A RAISED |
| FLOOR? IF SO, PLEASE INDICATE THE |
| REQUIRMENTS/ SD UNDER FLR. |
| 8.2 |
| |
| 12) NOTE: PLEASE CLARIFY RISER, IS THE |
| "EXISTING TENANT" BEING SHOWN ON THE |
| RISER ANOTHER TENANT SPACE OR IS THIS |
| THE EXISTING TENANT RISER FOR THIS |
| SPACE? |
| AS SHOWN, THERE SEEMS TO BE AN EXISTING |
| TENANT AND THIS NEW BUILD OUT IS NOTW |
| TAPPING THE EXISTING METER AS SHOWN?? |
| THIS IS NOT CLEAR AT THIS TIME. |
| 215.5 |
| |
| 13) NOTE: PLEASE PROVIDE EXISTING , OR |
| NEW METER SIZE AND WHERE THE |
| DISCONNECTING MEANS FOR SERVICE IS |
| LOCATED AND THE OCP AND SIZE OF TENANT |
| SERVICE DISCONNECT. |
| CURRENTLY THIS IS NOT SHOWING ANY MAIN, |
| AND A 42 CIRCUIT MLO FOR TENANTS |
| DISCONNECTING MEANS. |
| 215.5,240.4,310.16,230.70 ETC |
| |
| 14) NOTE: PLEASE INDICATE TH ACTUAL |
| ATTACHMENT FOR THE GROUNDING ELECTRODE |
| OF THE NEW SEPARATELY DERIVED |
| TRANSFORMERS. |
| 250.66, 250.30 |
| THE NOTE ON PLANS NEEDS TO BE SHOWN. |
| |
| 15) NOTE: PLEASE SEE MININUM CLEARENCES |
| FOR TRANSFORMER AND PANELS DO NOT MEET |
| 110.26, 450.13,450.9 ETC |
| PLEASE SEE PLANS MENTIONS THESE TO BE |
| FLR MOUNTED WHICH WOULD PLACE THEM |
| DIRECTLY INFRONT OF PANEL(S). |
| |
| 16) NOTE: PLEASE VERIFY LOAD |
| CALCULATIONS WHICH SHOULD INDICATE ALL |
| CONTINOUS LOADS AT 125%. |
| PLEASE SEE THE DEMAND IS SHOWN AS 1.25 |
| ON PANELS, BUT NOT ON MAIN PANEL AND THE |
| CONTINUOUS LOADS DO NOT NOT SEEM TO HAVE |
| BEEN CARRIED OVER. |
| 215.3,230.42 |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS |
| FROM OTHER TRADES WHICH MAY AFFECT |
| ELECTRICAL PLANS AND DESIGN. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |