Plan Review Notes
Plan Review Notes For Permit 06051212
Permit Number 06051212
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-19 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT ***********
  
 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL MATERIALS AND
 LABOR (EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED).
 PLEASE SEE UPGRADE , AND SPECIALLY
 DESIGNED LIGHTING CONTROL SYSTEMS ETC
 SHALL ALOS BE INCLUDED IN VALUE IF SHOWN
 ON PLANS.
 ALL PERMANANTLY INSTALLED SYSTEMS.
 FBC ADMINISTRATIVE SECTION 108.3 AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON ALL TITLE BLOCKS ON PLANS.
 PLEASE SEE MISSING ARCHITECTURAL FIRM
 CERTIFICATE OF AUTHORIZATION #.
 PLEASE SEE MISSING ENGINEERING FIRM CA#.
 PLEASE SEE MISSING THE PRINTED NAME AND
 PRINTED LICENSE # OF SAID ARCHITECT.
 PLEASE SEE ALL OF THE ABOVE IS REQUIRED
 PER FLORIDA ADMINISTRATIVE CODES
 61G1-16.004, 61G15-23.002, FLORIDA
 STATUES 481.219, AND FS471.023
 ** THIS IS REQUIRED OF ALL TRADES AND
 FOR ALL SHEET WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 WHICH
 PASSED A RULING IN FEB 04 WHICH REQUIRED
 ALL ENGINEER'S SEALS TO CONTAIN THE
 WORDING OF "LICENSE" IN SEAL. PLEASE SEE
 THAT ALL SEALS WITH THE WORDING OF
 "CERTIFICATE" ARE NOT LONGER ACCEPTABLE.
  
 4) NOTE: PLEASE SEE THAT PLANS ARE NOT
 DATED BY THE ARCHITECT OR ENGINEER AS
 REQUIRED UNDER FS 481.221 AND 471.025
  
 5) NOTE: PLEASE SEE CORRECTED ENERGY
 CODE CALCULATIONS SHAL BE DESIGNED UNDER
 FBC 2004.
 PLEASE SEE THEY CURRENTY INDICATE THE
 2001 ICC.
 PLEASE BE SURE THEY ARE SIGNED , DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1,
 13-415.2.ABC.1
  
 6) NOTE: PLEASE BE SURE PLANS INCLUDIGN
 ELECTRICAL REFLECT THE CURRNT CODE IN
 EFFECT FOR DESIGN.
 PLEASE SEE PLANS SHOULD INCLUDE THE
 FOLLOWING AT A MIN.
 2002 NFPA-70, (2005 SHOWN), 2003
 NFPA-101, NFPA-72 2002, NFPA-75 2003.
  
 7) NOTE: PLEASE CLARIFY LIGHTING
 CONTROLS FOR ALL ROOMS AS SOME COULD NOT
 BE LOCATED FOR THE OVER RIDE DEVICES AS
 REQUIRED.
 FBC 13-415.1.ABC.1.1, .1.2 ETC.
 1205,1202,1203,1201
 ** PLEASE SPECIFY TIME LIMITS ON
 DEVICES. CAN BE A "TYPICAL" NOT FOR NO
 MORE THAN 30 MINS FOR OS TYOE DEVICES
 AND 4HRS FOR TIMED TYPE DEVICES.
 ** PLEASE SEE A OSZ2 DEVICE IS SHOWN ON
 PLANS, HOWEVER COULD NOT LOCATED THIS ON
 LEGEND?
  
 8) NOTE:PLEASE SEE FIRE REVIEW
 COMMENTS AS TYPE OF "ELEC LOCK" FOR
 ACCESS CONTROLS NEED TO BE CLARIFIED.
 PLEASE SEE THAT IN THE EVENT OF POWER
 FAILURE, EGREES SHALL NOT IMPEDED.
  
 9) NOTE: PLEASE SEE THAT PLANS CLEARLY
 INDICATE THE FLR AND SUITE NUMBER IN
 TITLE BLOCK.
 FAC 61G1-16.004
  
 10) NOTE: PLEASE KNOW, AN "ALTERNATE"
 SYSTEM IS BEING SHOWN FOR THE IT ROOM.
 PLEASE KNOW, IF THIS SYSTEM IS BEING
 PROPOSED THEN IT SHOULD BE ON PLANS, IF
 NOT THIS SHOULD BE REMOVED. IF THIS
 SYSTEM IS GOING TO BE INSTALLED, PLEASE
 PROVIDE ALL MANUFACTURES SPCES/CUT
 SHEETS INDICATE A LISTING FROM A NRTL.
 215.5
  
 11) NOTE: PLEASE CLARIFY ROOM BEING
 INDICATE AS AN "IT" ROOM ON PLANS WHICH
 SHALL MEET NFPA-75 AND NEC 645.
 PLEASE CLARIFY IF THERE IS A RAISED
 FLOOR? IF SO, PLEASE INDICATE THE
 REQUIRMENTS/ SD UNDER FLR.
 8.2
  
 12) NOTE: PLEASE CLARIFY RISER, IS THE
 "EXISTING TENANT" BEING SHOWN ON THE
 RISER ANOTHER TENANT SPACE OR IS THIS
 THE EXISTING TENANT RISER FOR THIS
 SPACE?
 AS SHOWN, THERE SEEMS TO BE AN EXISTING
 TENANT AND THIS NEW BUILD OUT IS NOTW
 TAPPING THE EXISTING METER AS SHOWN??
 THIS IS NOT CLEAR AT THIS TIME.
 215.5
  
 13) NOTE: PLEASE PROVIDE EXISTING , OR
 NEW METER SIZE AND WHERE THE
 DISCONNECTING MEANS FOR SERVICE IS
 LOCATED AND THE OCP AND SIZE OF TENANT
 SERVICE DISCONNECT.
 CURRENTLY THIS IS NOT SHOWING ANY MAIN,
 AND A 42 CIRCUIT MLO FOR TENANTS
 DISCONNECTING MEANS.
 215.5,240.4,310.16,230.70 ETC
  
 14) NOTE: PLEASE INDICATE TH ACTUAL
 ATTACHMENT FOR THE GROUNDING ELECTRODE
 OF THE NEW SEPARATELY DERIVED
 TRANSFORMERS.
 250.66, 250.30
 THE NOTE ON PLANS NEEDS TO BE SHOWN.
  
 15) NOTE: PLEASE SEE MININUM CLEARENCES
 FOR TRANSFORMER AND PANELS DO NOT MEET
 110.26, 450.13,450.9 ETC
 PLEASE SEE PLANS MENTIONS THESE TO BE
 FLR MOUNTED WHICH WOULD PLACE THEM
 DIRECTLY INFRONT OF PANEL(S).
  
 16) NOTE: PLEASE VERIFY LOAD
 CALCULATIONS WHICH SHOULD INDICATE ALL
 CONTINOUS LOADS AT 125%.
 PLEASE SEE THE DEMAND IS SHOWN AS 1.25
 ON PANELS, BUT NOT ON MAIN PANEL AND THE
 CONTINUOUS LOADS DO NOT NOT SEEM TO HAVE
 BEEN CARRIED OVER.
 215.3,230.42
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  