2006-06-20 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06051212 |
| ADD: 777 S FLAGLER# 1200 |
| CONT: HEDRICK BROTHERS |
| TEL: (561)718-8341 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) SEE ELECTRICAL COMMENTS 2-5 ON |
| LICENSING LAWS FL S. S. 471/ 481 FOR |
| ENGINGEERS & ARCHITECTS. |
| |
| 3) SHEET A0.03 |
| 3A) PROJECT CODE DATA IS MISSING MINIMUM |
| BUILDING TYPE SEE TABLE 503. |
| |
| 3B) APPLICABLE CODE DATA LIST THE 2004 |
| FBC BUT NO MENTION TO THE 2004 FBC |
| EXISTING BUILDING CODE PROVIDE WHAT |
| LEVEL OF RENOVATION IS TO TAKE PLACE. |
| |
| 4) SHEET A7.00 DETAILS 7 & 8 BOTH REFER |
| TO DETAIL 1/ OF SHEET 9.00 MISSING? |
| |
| 5) BOTH OF THE DETAILS MENTIONED ABOVE |
| INDICATE THE USE OF WOOD PANELS, PROVIDE |
| ADDITIONAL INFORMATION. WOOD PANEL |
| FINISHES PROVIDE DOCUMENTATION TO BEING |
| TESTED TO ASTM E 84 OR NFPA 286. |
| 803.1/ 803.2. |
| |
| 6) DETAIL# 5/ A8.20 INDICATES THE USE OF |
| |
| 3/4" PANELING WITHOUT SOLID BACKING. |
| SEE 803.4.2,803.4.2 SET-OUT |
| CONSTRUCTION. |
| WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| BE OF FIRE-RESISTANCE-RATED OR |
| NONCOMBUSTIBLE CONSTRUCTION AND WALLS |
| ARE SET OUT OR CEILINGS ARE DROPPED |
| DISTANCES GREATER THAN SPECIFIED IN |
| SECTION 803.4.1 , CLASS A FINISH |
| MATERIALS SHALL BE USED EXCEPT WHERE |
| INTERIOR FINISH MATERIALS ARE PROTECTED |
| ON BOTH SIDES BY AN AUTOMATIC SPRINKLER |
| SYSTEM OR ATTACHED TO NONCOMBUSTIBLE |
| BACKING OR FURRING STRIPS INSTALLED AS |
| SPECIFIED IN SECTION 803.4.1 . THE |
| HANGERS AND ASSEMBLY MEMBERS OF SUCH |
| DROPPED CEILINGS THAT ARE BELOW THE MAIN |
| CEILING LINE SHALL BE OF NONCOMBUSTIBLE |
| MATERIALS, EXCEPT THAT IN TYPE III AND V |
| CONSTRUCTION, FIRE-RETARDANT-TREATED |
| WOOD SHALL BE PERMITTED. THE |
| CONSTRUCTION OF EACH SET-OUT WALL SHALL |
| BE OF FIRE-RESISTANCE-RATED CONSTRUCTION |
| AS REQUIRED ELSEWHERE IN THIS CODE. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |