2006-06-02 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. THE MASTER PERMIT #05120685 INDICATES
 A PROPOSED GENERATOR. NOTE: GAS PERMIT
 CAN NOT BE ISSUED UNTIL A GEN/RES PERMIT
 APPLICATION HAS BEEN APPLIED FOR AND
 APPROVED BY ZONING FOR GENERATOR
 LOCATION. THE GENERATOR COULD BE
 INDICATED ON THE DRAWING AS A FUTURE
 GENERATOR, WITH PIPING AT OWN RISK.
 2. PLEASE INDICATE THE MATERIAL TYPE IN
 THE DROP TO THE FIREPLACE, DRYER, AND
 THE RUN TO THE BBQ.
 3. THE GAS REGULATOR INDICATED FOR THE
 POOL IS UNDER SIZED. THE INDIVIDUAL LOAD
 CAPACITY FOR A MAXITROL 325-5 IS ONLY
 300,000 BTU/HR, POOL HEATER INDICATED ON
 DRAWING IS 400,000 BTU/HR, A MAXITROL
 325-7 IS REQUIRED. PLEASE SEE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 4. THE GAS REGULATOR INDICATED FOR THE
 THE HOUSE IS THE WRONG PIPE SIZE, A
 MAXITROL 325-3 IS 1/2", A 3/4", 325-5A
 REGULATOR IS REQUIRED. PLEASE SEE
 CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.
 5. THE CSST TO THE WATER HEATER IS UNDER
 SIZED PER TABLE 402.4(14) PLEASE SEE
 ATTACHED TABLE AND CORRECTED DRAWING FOR
 REFERENCE FOR RESUBMITTAL.
 6. PLEASE NOTE ON THE CORRECTED DRAWING
 THE SYSTEMS BREAK DOWN BETWEEN 2LB AND
 12" W.C. WITH THE LONGEST LENGTH AND THE
 TOTAL BTU'S INDICATED FOR EACH SYSTEM.
 IN THE FUTURE IN ORDER TO EXPIDITE PLAN
 REVIEW PLEASE HAVE THIS ON THE DRAWING.
 7. ONLY ONE CORRECTED DRAWING IN RED
 INK.
  
 END OF COMMENTS:
  