2007-11-09 10:50:31** DENIEDREVISION **
  
  
 1) NOTE: PLEASE SEE PLANS AND RISER CALL FOR A NEW
 120AMP DISCONNECT AND PANEL HOWEVER 120AMP IS NOT A
 RECOGNIZED STANDARD SIZE OF OVER CURRENT PROTECTION.
 PLEASE SEE 240.6.
  
 2) NOTE: PLEASE COMPLETE PLANS AND RISER WITH ALL
 MINIMUM REQUIRED CONDUCTORS.
 240.4, 310.16
  
 3) NOTE: PLEASE SEE THAT THE PLANS ARE REQUIRED TO BE
 SIGNED BY THE DESIGNER OF RECORD.
 FBC 106.1.2, 106.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  