2007-11-09 10:50:31 | ** DENIEDREVISION ** | | | | | | 1) NOTE: PLEASE SEE PLANS AND RISER CALL FOR A NEW | | 120AMP DISCONNECT AND PANEL HOWEVER 120AMP IS NOT A | | RECOGNIZED STANDARD SIZE OF OVER CURRENT PROTECTION. | | PLEASE SEE 240.6. | | | | 2) NOTE: PLEASE COMPLETE PLANS AND RISER WITH ALL | | MINIMUM REQUIRED CONDUCTORS. | | 240.4, 310.16 | | | | 3) NOTE: PLEASE SEE THAT THE PLANS ARE REQUIRED TO BE | | SIGNED BY THE DESIGNER OF RECORD. | | FBC 106.1.2, 106.5 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTIONS SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|