Plan Review Notes
Plan Review Notes For Permit 06051149
Permit Number 06051149
Review Stop B
Sequence Number 4
Notes
Date Text
2007-06-28 18:22:58 
 DENIED
  
 1)THE ATTIC ACCESS CANNOT BE INSTALLED IN THE FLAT
 ROOF AREA PLEASE REVISE.
  
 2)PLEASE PROVIDE THE FLORIDA STATEWIDE PRODUCT
 APPROVALS FOR 8" CASTCRETE LINTELS AND THE ROOF PRODUCT
 FOR THE FLAT ROOF. ASPHALT SHINGLES CANNOT BE USED ON
 ROOF SLOPES LESS THAN 2/12
  
 3)TRUSS ENGINEERING MUST BE SIGNED AND SEALED BY THE
 TRUSS MANUFACTURERS DESIGN PROFESSIONAL.
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
 PLEASE DO NOT ATTACH PRODUCT APPROVALS TO DRAWING
 SETS.
  
 BLDG PLAN REVIEW