2007-03-01 09:17:04 | *** UNSAT 3RD REVIEW *** |
| |
| ** PLEASE SEE SCOPE OF WORK AND PLANS HAS NOW |
| COMPLETELY CHANGED. PLEASE SEE COMMENTS. |
| |
| 1) NOTE: PLEASE SEE PLANS NOW CALL FOR FAMILY ROOM AS |
| EXISTING WHEREAS THE PREVIOUS TWO SETS OF PLANS |
| SUBMITTED INDICATED THIS AREA AS A NEW PROPOSED |
| ADDITION. PLEASE CLARIFY THIS AS REVIEW IS NOW CONFUSED |
| OVER SEPARATE PLANS FOR NEW AND EXISTING. |
| FBC 106.1.2 |
| |
| 2) NOTE: PLEASE SEE FBC R313 FOR NEW SMOKE ALARMS |
| NEEDED. PLEASE ALSO SEE NOTE BELOW. |
| ** |
| PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| ALARMS. |
| THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| FOR OTHER NEW HOMES. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE*. |
| |
| 3) NOTE: PLEASE SEE RISER AND PANEL AND NOTES FOR PANEL |
| DO NOT CORRELATE. SHOWS 200AMP MAIN BREAKER ON A 150AMP |
| PANEL AND ALSO SHOWS A 150AMP RATED MAIN?? |
| 106.1.2. |
| NEC 230.70, 310.16, 240.4 ETC |
| |
| 4) NOTE: PLEASE SEE THE SEALS ON PLANS ARE NOT CLEAR |
| AND VISIBLE ON PLANS AS REQUIRED PER FAC 61G15-23.001, |
| .002 AND FS 471.025. |
| THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| |
| 5) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52, |
| REDLINED IN ADDITION. |
| |
| 6) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI PER |
| 210.8A6. |
| |
| 7) NOTE: PLEASE SEE PLANS INDICATE A NEW STOVE, YET NO |
| RECEPTACLE OUTLET IS BEING SHOWN FOR THIS? PLEASE ALSO |
| SEE THAT THE REFRIGERATOR IS BEING SHOWN THE SAME WAY. |
| PANEL SCHEDULE INDICATES BOTH OF THESE. |
| PLEASE CORRELATE. |
| 106.1.2. |
| |
| 8) NOTE:PLEASE SEE DISHWASHER AND DISPOSAL BEING |
| SHOWN ON THE SAME SINGLE POLE CIRCUIT WHICH WILL PLACE |
| LOAD ON THIS CIRCUIT WHICH EXCEEDS THAT OF THE RATING |
| OF SAID BREAKER. |
| PLEASE SEE 210.4. |
| PLEASE SEE 240, 310.16, 422ETC |
| PLEASE SEE FBC 106.3.5.4 |
| |
| 9) NOTE: PLEASE SEE PANEL SCHEDULE WHICH IS MISSING THE |
| TWO REQUIRED SMALL APPLIANCE CIRCUITS AS SHOWN IN LOAD |
| CALCULATIONS. |
| 210.52B1, 210.11C1, 220.16 |
| |
| 10) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR |
| THE AHU IS BEING SHOWN IS HIGH FOR A UNIT WHICH IS |
| BEING SHOWN AS 7.5KW ON LOAD CALCULATIONS. PLEASE SEE |
| THE MECHANICAL PLANS INDICATE THIS UNIT AS 10KW. IF |
| INDEED THIS IS THE CASE, THEN REVISE THE LOAD |
| CALCULATIONS AND NOT THE OVER CURRENT PROTECTION OF THE |
| BREAKER AS SHOWN ON PANEL SCHEDULE. |
| 240.4, 310.16 ETC |
| PLEASE SEE 220.31B FOR LOAD CALCULATIONS FOR ADDITIONS |
| TO EXISTING DWELLINGS. |
| PLEASE SEE THAT PLANS SEEM TO BE INDICATING A NEW CU, |
| OR IS THIS RELOCATED. PLEASE SEE THE CLEARANCE REQUIRED |
| FOR A/C EQUIPMENT ON THE ELECTRICAL PLANS DOES NOT SEEM |
| TO BE MET FOR MINIMUM REQUIRED FOR CU EQUIPMENT. PLEASE |
| SEE THE MECHANICAL PLANS ARE DIFFERENT. |
| 110.26 AND SEE MECHANICAL CODE FOR THEIR MINIMUM |
| REQUIRED. |
| |
| 11) NOTE: PLEASE SEE MISSING GFI FOR NEW CU. 210.63, |
| 210.8A2 |
| |
| 12) NOTE: PLEASE SEE OTHER CIRCUITS BEING SHOWN ON |
| PANEL SCHEDULE WHICH ARE SHOWN AS BLANK OR OTHER 2-POLE |
| BREAKERS AS SPARES?? |
| PLEASE CLARIFY. |
| PLEASE INDICATE THE CIRCUITS FOR NEW WIRING AND ANY |
| EXISTING AS SUCH. |
| 408.6, 240.4, 310.16, |
| FBC 106.3.5.4 |
| |
| 13) NOTE: ** PLEASE KNOW THAT ONE SET OF EACH SET OF |
| PLANS WILL BE RETAINED AND PLACED WITH PREVIOUS HELD |
| PLANS FOR THE SAME DESIGNER OF RECORD AND FORWARDED TO |
| THE STATE OF FLORIDA, AND FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS. PLEASE SEE FS 471.025(3) |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |