Plan Review Notes
Plan Review Notes For Permit 06051149
Permit Number 06051149
Review Stop E
Sequence Number 3
Notes
Date Text
2007-03-01 09:17:04*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SCOPE OF WORK AND PLANS HAS NOW
 COMPLETELY CHANGED. PLEASE SEE COMMENTS.
  
 1) NOTE: PLEASE SEE PLANS NOW CALL FOR FAMILY ROOM AS
 EXISTING WHEREAS THE PREVIOUS TWO SETS OF PLANS
 SUBMITTED INDICATED THIS AREA AS A NEW PROPOSED
 ADDITION. PLEASE CLARIFY THIS AS REVIEW IS NOW CONFUSED
 OVER SEPARATE PLANS FOR NEW AND EXISTING.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE FBC R313 FOR NEW SMOKE ALARMS
 NEEDED. PLEASE ALSO SEE NOTE BELOW.
 **
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
  
 3) NOTE: PLEASE SEE RISER AND PANEL AND NOTES FOR PANEL
 DO NOT CORRELATE. SHOWS 200AMP MAIN BREAKER ON A 150AMP
 PANEL AND ALSO SHOWS A 150AMP RATED MAIN??
 106.1.2.
 NEC 230.70, 310.16, 240.4 ETC
  
 4) NOTE: PLEASE SEE THE SEALS ON PLANS ARE NOT CLEAR
 AND VISIBLE ON PLANS AS REQUIRED PER FAC 61G15-23.001,
 .002 AND FS 471.025.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52,
 REDLINED IN ADDITION.
  
 6) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI PER
 210.8A6.
  
 7) NOTE: PLEASE SEE PLANS INDICATE A NEW STOVE, YET NO
 RECEPTACLE OUTLET IS BEING SHOWN FOR THIS? PLEASE ALSO
 SEE THAT THE REFRIGERATOR IS BEING SHOWN THE SAME WAY.
 PANEL SCHEDULE INDICATES BOTH OF THESE.
 PLEASE CORRELATE.
 106.1.2.
  
 8) NOTE:PLEASE SEE DISHWASHER AND DISPOSAL BEING
 SHOWN ON THE SAME SINGLE POLE CIRCUIT WHICH WILL PLACE
 LOAD ON THIS CIRCUIT WHICH EXCEEDS THAT OF THE RATING
 OF SAID BREAKER.
 PLEASE SEE 210.4.
 PLEASE SEE 240, 310.16, 422ETC
 PLEASE SEE FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE WHICH IS MISSING THE
 TWO REQUIRED SMALL APPLIANCE CIRCUITS AS SHOWN IN LOAD
 CALCULATIONS.
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR
 THE AHU IS BEING SHOWN IS HIGH FOR A UNIT WHICH IS
 BEING SHOWN AS 7.5KW ON LOAD CALCULATIONS. PLEASE SEE
 THE MECHANICAL PLANS INDICATE THIS UNIT AS 10KW. IF
 INDEED THIS IS THE CASE, THEN REVISE THE LOAD
 CALCULATIONS AND NOT THE OVER CURRENT PROTECTION OF THE
 BREAKER AS SHOWN ON PANEL SCHEDULE.
 240.4, 310.16 ETC
 PLEASE SEE 220.31B FOR LOAD CALCULATIONS FOR ADDITIONS
 TO EXISTING DWELLINGS.
 PLEASE SEE THAT PLANS SEEM TO BE INDICATING A NEW CU,
 OR IS THIS RELOCATED. PLEASE SEE THE CLEARANCE REQUIRED
 FOR A/C EQUIPMENT ON THE ELECTRICAL PLANS DOES NOT SEEM
 TO BE MET FOR MINIMUM REQUIRED FOR CU EQUIPMENT. PLEASE
 SEE THE MECHANICAL PLANS ARE DIFFERENT.
 110.26 AND SEE MECHANICAL CODE FOR THEIR MINIMUM
 REQUIRED.
  
 11) NOTE: PLEASE SEE MISSING GFI FOR NEW CU. 210.63,
 210.8A2
  
 12) NOTE: PLEASE SEE OTHER CIRCUITS BEING SHOWN ON
 PANEL SCHEDULE WHICH ARE SHOWN AS BLANK OR OTHER 2-POLE
 BREAKERS AS SPARES??
 PLEASE CLARIFY.
 PLEASE INDICATE THE CIRCUITS FOR NEW WIRING AND ANY
 EXISTING AS SUCH.
 408.6, 240.4, 310.16,
 FBC 106.3.5.4
  
 13) NOTE: ** PLEASE KNOW THAT ONE SET OF EACH SET OF
 PLANS WILL BE RETAINED AND PLACED WITH PREVIOUS HELD
 PLANS FOR THE SAME DESIGNER OF RECORD AND FORWARDED TO
 THE STATE OF FLORIDA, AND FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. PLEASE SEE FS 471.025(3)
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]