2007-03-31 13:24:56 | |
| |
| DENIED |
| |
| ****NOTE**** |
| THE FOLLOWING COMMENTS FROM THE 2ND BUILDING REVIEW |
| WERE NOT ADDRESSED. |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| 3) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL. *****NOT SIGNED AND DATED BY |
| OWNER/AGENT****** |
| |
| 6) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC*. |
| ******REVIEWED AND APPROVED BY PERSON RESPONSIBLE FOR |
| DRAWINGS******* |
| |
| 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT |
| APPLICATION OR BEFORE INSTALLATION THAT |
| HAVE BEEN REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD. |
| |
| 9) PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| COMPLIANCE WITH THE REQUIREMENTS OF R403.1 ******THE |
| DRAINAGE PROVISION IS TO SHOW POSITIVE DRAINAGE AWAY |
| FROM NEW STRUCTURE AND ALSO SHOW THAT DOES NOT FLOW |
| ONTO ADJOINING PROPERTY****** |
| |
| ******NEW COMMENTS****** |
| |
| 1) THE PROVIDED ATTIC ACCESS IS THROUGH THE PROPOSED |
| GIRDER BEAM PLEASE RELOCATE TO AN AREA THAT PROVIDES |
| 30" OF HEADROOM ABOVE ACCESS. |
| |
| 2) UNDER THE EXISTING BUILDING CODE ADDITIONS ARE |
| TREATED AS NEW CONSTRUCTION AND THE ACCESSIBILITY |
| REQUIREMENTS OF ONE BATHROOM WITH A MIN 29" CLEAR |
| OPENING WITH DOOR AT 90 DEGREES IS REQUIRE PER R322.1.1 |
| FBC |
| |
| 3) UNDER THE EXISTING BUILDING CODE ADDITIONS, SMOKE |
| ALARMS SHALL BE PROVIDED IN THE EXISTING PORTIONS OF |
| THE BUILDING PER 904.2 FBC (EXISTING) |
| |
| 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL COVER |
| SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| SUBMITTED APPLICATIONS WILL BE DENIED. |
| PLEASE NOTE THAT I HAVE PRINTED THESE FOR YOUR WINDOWS |
| AND PRECAST LINTELS |
| |
| 5) PROVIDE NEW UPDATED MIAMI-DADE NOA'S FOR THE |
| OAKRIDGE PRO 40 SHINGLES AS THIS NOA HAS EXPIRED. ALSO |
| A NOA WILL BE REQUIRED FOR THE FLAT ROOF I WOULD |
| SUGGEST THAT YOUR ROOFING CONTRACTOR SUPPLIES YOU WITH |
| THIS PRODUCT APPROVAL AS THERE ARE THOUSANDS OF |
| VARIATIONS AND THE EXACT ONE MUST BE CHOSEN AND |
| INSTALLED TO PASS INSPECTION. PROVIDE PRODUCT APPROVAL |
| FOR MULLION WHERE 2 OR MORE WINDOWS ARE JOINED TOGETHER |
| AS IN MASTER BEDROOM. |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |