Plan Review Notes
Plan Review Notes For Permit 06051149
Permit Number 06051149
Review Stop B
Sequence Number 3
Notes
Date Text
2007-03-31 13:24:56 
  
 DENIED
  
 ****NOTE****
 THE FOLLOWING COMMENTS FROM THE 2ND BUILDING REVIEW
 WERE NOT ADDRESSED.
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 3) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. *****NOT SIGNED AND DATED BY
 OWNER/AGENT******
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*.
 ******REVIEWED AND APPROVED BY PERSON RESPONSIBLE FOR
 DRAWINGS*******
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 9) PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 ******THE
 DRAINAGE PROVISION IS TO SHOW POSITIVE DRAINAGE AWAY
 FROM NEW STRUCTURE AND ALSO SHOW THAT DOES NOT FLOW
 ONTO ADJOINING PROPERTY******
  
 ******NEW COMMENTS******
  
 1) THE PROVIDED ATTIC ACCESS IS THROUGH THE PROPOSED
 GIRDER BEAM PLEASE RELOCATE TO AN AREA THAT PROVIDES
 30" OF HEADROOM ABOVE ACCESS.
  
 2) UNDER THE EXISTING BUILDING CODE ADDITIONS ARE
 TREATED AS NEW CONSTRUCTION AND THE ACCESSIBILITY
 REQUIREMENTS OF ONE BATHROOM WITH A MIN 29" CLEAR
 OPENING WITH DOOR AT 90 DEGREES IS REQUIRE PER R322.1.1
 FBC
  
 3) UNDER THE EXISTING BUILDING CODE ADDITIONS, SMOKE
 ALARMS SHALL BE PROVIDED IN THE EXISTING PORTIONS OF
 THE BUILDING PER 904.2 FBC (EXISTING)
  
 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED.
 PLEASE NOTE THAT I HAVE PRINTED THESE FOR YOUR WINDOWS
 AND PRECAST LINTELS
  
 5) PROVIDE NEW UPDATED MIAMI-DADE NOA'S FOR THE
 OAKRIDGE PRO 40 SHINGLES AS THIS NOA HAS EXPIRED. ALSO
 A NOA WILL BE REQUIRED FOR THE FLAT ROOF I WOULD
 SUGGEST THAT YOUR ROOFING CONTRACTOR SUPPLIES YOU WITH
 THIS PRODUCT APPROVAL AS THERE ARE THOUSANDS OF
 VARIATIONS AND THE EXACT ONE MUST BE CHOSEN AND
 INSTALLED TO PASS INSPECTION. PROVIDE PRODUCT APPROVAL
 FOR MULLION WHERE 2 OR MORE WINDOWS ARE JOINED TOGETHER
 AS IN MASTER BEDROOM.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  