2006-10-15 20:50:20 | ********* UNSAT2ND REVIEW ************* |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG |
| WIHT SOME NEW COMMENTS DUE TO THE PLANS SUBMITTED FOR |
| THIS REVIEW. |
| |
| |
| 1)NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE:NO, SAME NOTE. PLEASE STILL MISSING |
| DISCONNETC FOR WH AND MIN CLEARENACE FOR BOTH THE CU |
| AND AHU. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| ]PLEASE INCLUDE ALL MIN |
| CLEARENCES FOR DISCONNECTS FOR CU, AHU |
| AND WATER HEATER. |
| 110.26. |
| PLEASE ALSO INCLUDE ALL DISCONNECTS. |
| 440.11,422.31 ETC. |
| |
| 7) NOTE: NO, PLEASE STILL SEE MISSINGRECEPTS AS |
| REQUIRED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING RECEPTS |
| REQ'D PER 210.52 |
| |
| 8) NOTE:OK. |
| |
| 9) NOTE: OK, HOWEVER STILL SEE ZONING COMMENTS AS THIS |
| MAY AFFECT PLANS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE SUBSTANTIAL COMMENTS |
| FROM ZONING WHICH WILL AFFECT PLANS AND |
| DESIGN. |
| |
| 10) NOTE: OK. |
| |
| ** NEW NOTE ** |
| 11) NOTE: PLEASE SEE NOTE BELOW WHICH REQUESTED ALL |
| OLD/VOIDED SHEETS TO BE REMOVED AND INSERT NEW SHEETS |
| INTO COMPLETE SETS FOR REVIEW AND PROCESSING. PLEASE |
| SEE THIS WAS NOT DONE. SHEETS ARE LOOSE AND NOT IN |
| SETS. PLEASE KNOW, WHEN PLANS COME BACK AND THIS IS NOT |
| DOWN, PLANS WILL BE REQUIRED TO BE PICKED UP BEFORE |
| REVIEWS WILL COMMENCE. |
| |
| ** PREVIOUS NOTE** |
| ** WHEN RESUBMITTING PLANS, PLEASE BE |
| SURE TO COMPLETELT REMOVE ANY OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETED SETS FOR REVIEW |
| AND STAMPING. |
| PLEASE SUBMIT ONLY ONE COPY OF THE |
| OLD/VOIDED SHEETS. |
| |
| 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| THIS IS ONLY A NOTICE GIVEN AT THIS TIEM, HOWEVER |
| ELECTRICAL PLANS ARE BEING RETAINED. |
| |
| 13) NOTE: PLEASE CORRELATE RISER AND PLANS AS PLANS |
| SHOW A MAIN DISCONNECT AND RISER DOES NOT. |
| FBC 106.1.2, 106.3.5.4 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |