Plan Review Notes
Plan Review Notes For Permit 06051131
Permit Number 06051131
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENGLERT SERIES 1300 METAL PANELS
 (DADE COUNTY NOA #03-0108.03):
 A) MAXIMUM DESIGN PRESSURES FOR THIS
 SYSTEM IS -60PSF. DESIGN PRESSURES FOR
 CORNER AND PERIMETER AREAS ARE HIGHER
 FOR THIS AREA. SEE TABLE 1609.6B FBC
 2004. NEED TO PROVIDE CALCULATIONS FOR
 INCREASED DESIGN PRESSURES AT THESE
 ZONES. ALL CALCULATIONS TO BE PERFORMED
 SIGNED AND SEALED BY ANY ONE OF THE
 PROFESSIONALS LISTED IN SYSTEM
 LIMITATION NUMBER 1. SEE PAGE 5 OF 6.
 B) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED. SEE ATTACHED COPY OF
 CITY POLICY FOR RE-ROOFING PERMITS AND
 REQUIRED INFORMATION TO BE SUBMITTED.
 C) SPECIFY MEAN ROOF HEIGHT.
 D) SPECIFY ROOF PITCH.
  
 2- FLAT ROOF SYSTEM:
 A) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED AND SPECIFIC FASTENING
 OPTION TO BE USED AS REQUIRED BY CITY
 POLICY FOR RE-ROOFING PERMITS.
 B) PROVIDE FLORIDA PRODUCT APPROVAL
 UPDATED COVER PAGE WITH FBC 2004 CODE
 VERSION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  