Plan Review Notes For Permit 06051118 |
Permit Number |
06051118 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-09 00:00:00 | | | INCOMPLETE INFORMATION. PLEASE PROVIDE | | THE FOLLOWING: | | | | 1} PROVIDE A SITE PLAN INDICATING THE | | LOCATION OF ALL SERVICE EQUIPMENT SO | | THAT COMPLIANCE WITH ARTICLE 230 CAN BE | | REVIEWED. | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2. | | | | 3} THE LOAD CALC INCLUDES 90.5 AMPS | | "TOTAL NEW LOAD", NO APPLICATIONS WERE | | SUBMITTED FOR NEW WORK. | | | | 4} CUSTOM MECHANICAL INC. WAS ISSUED A | | PERMIT FOR SERVICE CHANGE #05031077 THAT | | FAILED INSPECTION AND WAS NOT CLOSED | | OUT. PLEASE INDICATE IN WRITING THAT YOU | | WANT THAT PERMIT CLOSED AND HAVE APPLIED | | FOR A NEW PERMIT TO COVER THE SERVICE | | CHANGE. | | | | 5} INDICATE ALL WORK PROPOSED, OR WORK | | DONE WITHOUT A PERMIT THAT IS REQUIRED | | TO BE PERMITTED, THAT IS UNDER THE SCOPE | | OF THIS APPLICATION, ON THE DESCRIPTION | | OF WORK. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | |
|