Plan Review Notes
Plan Review Notes For Permit 06051118
Permit Number 06051118
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-09 00:00:00 
 INCOMPLETE INFORMATION. PLEASE PROVIDE
 THE FOLLOWING:
  
 1} PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF ALL SERVICE EQUIPMENT SO
 THAT COMPLIANCE WITH ARTICLE 230 CAN BE
 REVIEWED.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 3} THE LOAD CALC INCLUDES 90.5 AMPS
 "TOTAL NEW LOAD", NO APPLICATIONS WERE
 SUBMITTED FOR NEW WORK.
  
 4} CUSTOM MECHANICAL INC. WAS ISSUED A
 PERMIT FOR SERVICE CHANGE #05031077 THAT
 FAILED INSPECTION AND WAS NOT CLOSED
 OUT. PLEASE INDICATE IN WRITING THAT YOU
 WANT THAT PERMIT CLOSED AND HAVE APPLIED
 FOR A NEW PERMIT TO COVER THE SERVICE
 CHANGE.
  
 5} INDICATE ALL WORK PROPOSED, OR WORK
 DONE WITHOUT A PERMIT THAT IS REQUIRED
 TO BE PERMITTED, THAT IS UNDER THE SCOPE
 OF THIS APPLICATION, ON THE DESCRIPTION
 OF WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  