Plan Review Notes
Plan Review Notes For Permit 06051102
Permit Number 06051102
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-23 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- CONTRACTOR TO CLEARLY IDENTIFY
 SPECIFIC FLAT ROOF APPROVED ASSEMBLY TO
 BE INSTALLED AS REQUIRED BY CITY POLICY
 FOR RE-ROOFING PERMITS. SEE ATTACHED
 COPY OF THE POLICY.
  
 2- IF SELECTED INSULATED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE THE CALCULATIONS FOR ENHANCED
 UPLIFT PRESSURES AT CORNER AND PERIMETER
 AREAS. SEE TABLE 1609.6B FBC 2004 FOR
 CALCULATEDDESIGN PRESSURES AT CORNER
 AND PERIMETER AREAS. SEE ATTACHED COPY.
 CALCULATIONS TO BE DONE AS PER RAS 117.
 SEE LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 3- PROVIDE COVER PAGE OF FLORIDA PRODUCT
 APPROVAL AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 5- CONTRACTOR'S VALUATION IS TOO LOW.
 OWES $546.61 FOR UPDATED VALUATION.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712