Plan Review Notes For Permit 06051102 |
Permit Number |
06051102 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-06-23 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: | | 1- CONTRACTOR TO CLEARLY IDENTIFY | | SPECIFIC FLAT ROOF APPROVED ASSEMBLY TO | | BE INSTALLED AS REQUIRED BY CITY POLICY | | FOR RE-ROOFING PERMITS. SEE ATTACHED | | COPY OF THE POLICY. | | | | 2- IF SELECTED INSULATED ASSEMBLY IS | | LIMITED BY GENERAL LIMITATION #7, THEN | | PROVIDE THE CALCULATIONS FOR ENHANCED | | UPLIFT PRESSURES AT CORNER AND PERIMETER | | AREAS. SEE TABLE 1609.6B FBC 2004 FOR | | CALCULATEDDESIGN PRESSURES AT CORNER | | AND PERIMETER AREAS. SEE ATTACHED COPY. | | CALCULATIONS TO BE DONE AS PER RAS 117. | | SEE LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | | | 3- PROVIDE COVER PAGE OF FLORIDA PRODUCT | | APPROVAL AS REQUIRED BY CITY POLICY FOR | | RE-ROOFING PERMITS. SEE ATTACHED COPY. | | | | 4- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 5- CONTRACTOR'S VALUATION IS TOO LOW. | | OWES $546.61 FOR UPDATED VALUATION. | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|