2006-06-22 00:00:00 | ********** UNSAT ************ |
| |
| 1) NOTE: PLEASE SEE SITE SURVEY WHICH |
| WILL REQUIRE ALL SETBACKS AND DIMENSIONS |
| FROM DWELLING AND PROPERTY LINES. PLEASE |
| SEE THAT THE CLEARENCS OF THE GEN CAN |
| NOT BE VERIFIED AT THIS TIME. |
| 215.5 |
| |
| 2) NOTE: PLEASE PROVIDE A SERVICE |
| ENTRANCE RATED ATS WHICH DISCONNECTS |
| POWER FROM FPL AND GEN OR PROVIDE A |
| DISCONNECITNG MEANS FOR FEEDERS FROM GEN |
| ALSO. |
| CAN NOT VEIRFY THE MEANS OF DISCONNECT |
| FOR THE LINE SIDE POWER FROM FPL MEETING |
| 230.70,230.76,230.79. |
| PLEASE SEE 225.31-225.39 |
| PLEASE SEE SPECS SUBMITTED WILL NOT BE |
| ACCEPTABLE AS SHOWN. |
| |
| 3) NOTE: PLEASE INDICATE LOCATION OF ALL |
| EQUIPMENT ON A LAYOUT FOR HOUSE. |
| 215.. |
| |
| 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| PLEASE ALSO INDICATE THE RATING FOR ATS. |
| |
| 5) NOTE: PLEASE SEE LOAD CALCULATIONS |
| SUBMITTED SEEM TO BE MISSING MANY OTHER |
| LOADS IN DWELLING. |
| WASHER, LAUNDRY, DRYER, WATER HEATER, |
| PUUMPS ETC. |
| ANY GAS APPLIANCE SHALL BE INDICATED. |
| PLEASE PROVIDE A COMPLETE PANEL SCHEDULE |
| FOR INTENDED LOADS. |
| PLEASE KNOW, IF LOADS EXCEED RATING OF |
| GEN, LOAD SHEDDING MAY BE APPLIED, |
| HOWEVER SHOW DETAIL. |
| 702.5,220,220.16,220.18, ETC. |
| 215.5 |
| |
| 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE |
| LICENSE CONTRACTOR SHALL PRINT NAME AND |
| SIGN PLANS. |
| FBC 106.2.1, 106.3.2.1 ADMIN SECT AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| 7) NOTE: PLEASE SEE THAT VALUE SHALL BE |
| ADJUSTED TO INLCUDE ALL LABOR AND |
| MATERIALS EVEN IF ANY EQUIPMENT ETC IS |
| OWNER SUPPLIED. |
| FBC 108.3 ADMINISTRATIVE SECTION AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH. |
| ** PLEASE KNOW, IF VALUE IS NOT |
| ADJUSTED, ONE WILL BE CALCUALTE BY THIS |
| OFFICE USING MARSHALL'S/ SWIFT GUIDE AS |
| ADOPTED INTO THE FBC. |
| ANY INCREASE IN VALUE SHALL BE DONE WHEN |
| RE-SUBMITTIGN PLANS AND PERMIT |
| APPLICATION. |
| |
| 8) NOTE: PLEASE BE SURE THE MANUFACTURES |
| SPECS / CUT SHEETS SHALL INDICATE THE |
| MIN CLEARENCES SET BY THE MANUFACTURE. |
| 215.5 |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
2006-06-08 00:00:00 | NEEDS TO UPDATE VALUE FOR TOTAL SCOPE. |
| LOOK FOR REVIEW NOTES. FBC 108.3 |