Plan Review Notes For Permit 06051034 |
Permit Number |
06051034 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-06 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 SEC. 424.2 OR | | FBC-2004 RESIDENTIAL SEC. R4104 SWIM- | | MING POOLS: | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | REQUIRED FOR PLUMBING PLAN REVIEW: | | | | 1) THE PERMIT APPLICATION INDICATES NO | | POOL HEATER, BUT THE PRINT INDICATES A | | POOL HEATER IN THE POOL SPECIFICATIONS, | | EQUIPMENT LAYOUT, AND LEGEND PLEASE | | CORRELATE ONE WAY OR THE OTHER FOR | | RESUBMITTAL.(NOTE: IF THERE IS A POOL | | HEATER PLEASE PROVIDE TWO SETS OF | | MANUFACTURER CUT SHEETS INDICATING MAKE | | AND MODEL NUMBER OF HEATER BEING USED) | | 2) FBC-2004 SEC. 424.2.9, OR FBCR-2004 | | SEC. R4101.9 WATER SUPPLY, LOCAL ORD. | | #2853-95, BACKFLOW REQUIRED ON WATER | | SERVICE.(ADD TO NOTES) | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | TRANSMITTAL LETTER INDICATING HOW EACH | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | |
|