2006-06-13 00:00:00NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING THE CONTRACTOR TO DRAW THEIR
 OWN PLANS.
  
 2} SHEET ? SHOWS "OUT TO FPL"TO OR FROM
 A DISCONNECT.PLEASE CLARIFY.
  
 3} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 4} PLEASE LOCATE ALL SERVICE
 EQUIPMENT ON A SITE PLAN, METER
 ENCLOSURE, DISCONNECTS, PANELS,GENERATOR
 AND TRANSFER SWITCH, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  