2006-06-13 00:00:00 | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2. FBC AS | | AMENDED. THIS ARTICLE ALSO IS AN | | EXTRACTION FROM THE EXEMPTION IN CHAPTER | | 471 OF THE FLORIDA STATUTES , 471.003, | | ALLOWING THE CONTRACTOR TO DRAW THEIR | | OWN PLANS. | | | | 2} SHEET ? SHOWS "OUT TO FPL"TO OR FROM | | A DISCONNECT.PLEASE CLARIFY. | | | | 3} PROVIDE SPECIFICATIONS FOR THE | | TRANSFER SWITCH. | | | | 4} PLEASE LOCATE ALL SERVICE | | EQUIPMENT ON A SITE PLAN, METER | | ENCLOSURE, DISCONNECTS, PANELS,GENERATOR | | AND TRANSFER SWITCH, SO THAT COMPLIANCE | | WITH ARTICLES 225 AND 230 CAN BE | | REVIEWED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPARTMENT | | 561) 805-6718 | | |
|