2006-06-13 00:00:00 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2.ALL SHEETS. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT.THIS IS ALSO A | | REQUIREMENT OF THIS DEPARTMENT. | | | | 3} THERE IS A 150 AMP PANEL SHOWN ON ONE | | SHEET AND A 100 AMP METER ENCLOSURE ON | | ANOTHER SHEET. PLEASE LOCATE ALL SERVICE | | EQUIPMENT ON A SITE PLAN, METER | | ENCLOSURE, DISCONNECTS, PANELS,GENERATOR | | AND TRANSFER SWITCH, SO THAT COMPLIANCE | | WITH ARTICLES 225 AND 230 CAN BE | | REVIEWED. | | | | 4} PROVIDE SPEC'S FOR THE TRANSFER | | SWITCH. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPARTMENT | | 561) 805-6718 | | | | | | | | | | 4} |
|