Plan Review Notes
Plan Review Notes For Permit 06050978
Permit Number 06050978
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-13 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.ALL SHEETS.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.THIS IS ALSO A
 REQUIREMENT OF THIS DEPARTMENT.
  
 3} THERE IS A 150 AMP PANEL SHOWN ON ONE
 SHEET AND A 100 AMP METER ENCLOSURE ON
 ANOTHER SHEET. PLEASE LOCATE ALL SERVICE
 EQUIPMENT ON A SITE PLAN, METER
 ENCLOSURE, DISCONNECTS, PANELS,GENERATOR
 AND TRANSFER SWITCH, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.
  
 4} PROVIDE SPEC'S FOR THE TRANSFER
 SWITCH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  
  
  
  