2006-06-14 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 PANEL SERVICING THE LIFT INCLUDING ALL
 ADDED LOADS.
  
 2} PROVIDE CONDUCTOR AND CONDUIT SIZE
 AND TYPE. INDICATE THE OCP FOR THE
 CONDUCTORS.
  
 3} PROVIDE CIRCUIT NUMBERS FOR THE NEW
 LOADS, AND ORIGINATING PANEL
 DESIGNATION.
  
 4} INDICATE THE RATING FOR THE EQUIPMENT
 DISCONNECT AND IF ITS FUSED OR
 NON-FUSED.
  
 5} THE TITLE BLOCK OF THE ARCHITECTURAL
 FIRM MUST CONTAIN THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED BY THE
 STATE PER 61G1-16.004(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  