Plan Review Notes For Permit 06050976 |
Permit Number |
06050976 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-14 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE A LOAD CALCULATION FOR THE | | PANEL SERVICING THE LIFT INCLUDING ALL | | ADDED LOADS. | | | | 2} PROVIDE CONDUCTOR AND CONDUIT SIZE | | AND TYPE. INDICATE THE OCP FOR THE | | CONDUCTORS. | | | | 3} PROVIDE CIRCUIT NUMBERS FOR THE NEW | | LOADS, AND ORIGINATING PANEL | | DESIGNATION. | | | | 4} INDICATE THE RATING FOR THE EQUIPMENT | | DISCONNECT AND IF ITS FUSED OR | | NON-FUSED. | | | | 5} THE TITLE BLOCK OF THE ARCHITECTURAL | | FIRM MUST CONTAIN THE CERTIFICATE OF | | AUTHORIZATION NUMBER REQUIRED BY THE | | STATE PER 61G1-16.004(2). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPARTMENT | | 561) 805-6718 | | | | | | |
|