2006-06-15 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. SAME COMMENTS AS FIRST REVIEW.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2. FBC AS AMENDED. THIS
 ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA
 STATUTES , 471.003, ALLOWING YOU TO DRAW
 YOUR OWN PLANS. PLANS ARE NO TSIGNED.
  
 AS PER INSTRUCTION FROM THE BUILDING
 OFFICIAL, THIS DEPARTMENT REQUIRES ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD AS
 THE STATUTE INTENDS. PLEASE COMPLY WITH
 THIS STATUTE ON ALL DOCUMENTS DRAWN BY
 YOU AND SUBMITTED FOR REVIEW.
  
 PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.THIS IS ALSO A
 REQUIREMENT OF THIS DEPARTMENT. PLEASE
 PUT THE INFORMATION ON THE PLAN.
  
 THE LOAD CALCULATION MUST BE PER 220,
 PART II, OR 220.31(B), FOR EXISTING
 DWELLINGS. THE SMALL APPLIANCE
 CALCULATION IS NOT CORRECT. SEE 220.16.
 PLEASE RECALCULATE AND INDICATE WHICH
 ARTICLE IS BEING APPLIED.
  
  
 THE CODE REFERENCE NEC 384 IS FROM THE
 1996 CODE. PLEASE UPDATE CODE SECTIONS
 IF USING THEM AS REFERENCE.ALSO THE
 REFERENCES TO THE 1999 CODE ARE NOT
 COMPLIANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]