Plan Review Notes
Plan Review Notes For Permit 06050916
Permit Number 06050916
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-15 00:00:00 
  
  
  
  
 NONCOMPLIANT
  
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. SECOND REVIEW WITH SAME COMMENTS
 AS THE FIRST REVIEW.
  
 1}THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING YOU TO DRAW YOUR OWN PLANS .
  
 AS PER INSTRUCTION FROM THE BUILDING
 OFFICIAL, THIS DEPARTMENT REQUIRES ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD AS
 THE STATUTE INTENDS. PLEASE COMPLY WITH
 THIS STATUTE ON ALL DOCUMENTS DRAWN BY
 YOU AND SUBMITTED FOR REVIEW. THERE IS
 NO "PRINTED" NAME ON RESUBMITTED
 DOCUMENTS.
  
 2} THE LOAD CALCULATION MUST BE PER 220,
 PART II, OR 220.31(B), FOR EXISTING
 DWELLINGS.
 PLEASE RECALCULATE AND INDICATE WHICH
 ARTICLE IS BEING APPLIED. THE
 APPLICATIION INDICATES 5KW HEAT. THE
 LOAD CALCULATION IS FOR 7.5KW HEAT. IS
 THE 5000 WATTS BEING ADDED TO THE 7500?
 IF SO USE 220.31(B), IF NOT, SEE EXAMPLE
 IN THE 2002 NEC HANDBOOK.
  
 3} THIS APPLICATION INDICATES WIRING AN
 A/C SYSTEM, BUT NO DRAWINGS FOR
 LOCATION,CONDUIT OR CONDUCTOR TYPE AND
 SIZE WHERE SUBMITTED, ALL OF WHICH ARE
 REQUIRED FOR REVIEW.
  
 THE CODE REFERENCE NEC 384 IS FROM THE
 1996 CODE. PLEASE UPDATE CODE SECTIONS
 IF USING THEM AS REFERENCE.
  
 PLEASE SEE FLORIDA STATUTE #
 553.80(2)(B), REGARDING THE REQUIRED FEE
 THAT MUST BE IMPOSED AFTER THE NEXT
 REVIEW FOR THE SAME COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  