2006-06-02 00:00:00 | |
| NONCOMPLIANT |
| |
| |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| THE PERSON TAKING RESPONSIBILITY FOR THE |
| DESIGN MUST PRINT AND SIGN THEIR NAME TO |
| SAME PER 106.3.4.2. FBC AS AMENDED. THIS |
| ARTICLE ALSO IS AN EXTRACTION FROM THE |
| EXEMPTION IN CHAPTER 471 OF THE FLORIDA |
| STATUTES , 471.003, ALLOWING YOU TO DRAW |
| YOUR OWN PLANS . |
| |
| AS PER INSTRUCTION FROM THE BUILDING |
| OFFICIAL, THIS DEPARTMENT REQUIRES ALL |
| PLANS MUST CONTAIN THE PRINTED NAME AND |
| SIGNATURE OF THE DESIGNER OF RECORD AS |
| THE STATUTE INTENDS. PLEASE COMPLY WITH |
| THIS STATUTE ON ALL DOCUMENTS DRAWN BY |
| YOU AND SUBMITTED FOR REVIEW. |
| |
| PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT.THIS IS ALSO A |
| REQUIREMENT OF THIS DEPARTMENT. |
| |
| THE LOAD CALCULATION MUST BE PER 220, |
| PART II, OR 220.31(B), FOR EXISTING |
| DWELLINGS. |
| PLEASE RECALCULATE AND INDICATE WHICH |
| ARTICLE IS BEING APPLIED. |
| |
| THIS APPLICATION INDICATES WIRING AN A/C |
| SYSTEM, BUT NO DRAWINGS FOR LOCATION, |
| CONDUIT OR CONDUCTOR TYPE AND SIZE WHERE |
| SUBMITTED, ALL OF WHICH ARE REQUIRED FOR |
| REVIEW. |
| |
| THE CODE REFERENCE ?NEC 384? IS FROM THE |
| 1996 CODE. PLEASE UPDATE CODE SECTIONS |
| IF USING THEM AS REFERENCE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| WILLIAM R. TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| CONSTRUCTION SERVICES DEPARTMENT |
| 561) 805-6718 |
| |
| |